Function Explanation; F: Fundamental Functions - GE AF-300 P11 User Manual

Table of Contents

Advertisement

5.3 Function Explanation

F: Fundamental Functions

F00 Data protection
F 0 0
D A T A
P R T C
Setting range
0 : data can be changed
1 : data cannot be changed
This function protects the system by blocking any data
changes from the keypad panel.
Setting procedure:
0 to 1: Press the
STOP
and
change the value from 0 to 1, then press
FUNC
the
to validate the change.
DATA
STOP
1 to 0: Press the
and
to change the value from 1 to 0, then press
FUNC
the
key to validate the change.
DATA
F01 Frequency setting 1
F 0 1
F R E Q
C M D 1
This function determines the method to be used for setting
frequency.
NOTE: Use only one terminal - V2 or C1, exclusively.
0: Keypad operation (
1: Voltage input (terminal 12 and V2) (0 to +10 VDC,
0 to +5VDC)
2: Current input (terminal C1) (4 to 20 mA DC)
3: Voltage and current input (terminals 12 and C1)
4: Reversible operation with polarity (terminal 12)
(0 to ± 10 VDC)
5: Reversible operation with polarity (terminal 12 and V1
option) (0 to ± 10 VDC)
Related functions E01 to E09 (Set values 21)
6: Inverse mode operation (terminal 12 and V2)
(+10 to 0 VDC)
7: Inverse mode operation ( terminal C1)(20 to 4 mA DC)
8: UP/DOWN control 1 (initial freq. = 0 Hz
9: UP/DOWN control 2 (initial freq. = last value)
Related functions E01 to E09 (Set values 17, 18)
10. PATTERN operation
Related functions: C21 to C28
11: DI option or Pulse train input
For details, see instruction manual on options.
keys simultaneously to
keys simultaneously
or
key)
F02 Operation method
F 0 2
O P R
M E T H O D
This function determines the input method for operation
commands.
0: Keypad operation (
1: Terminal operation (
2: Terminal operation (
STOP
3: Terminal operation (
software
4: Terminal operation (
software
Note: GE start software prevents drive from restarting
when power is applied.
This function can only be changed when terminals
and
are open.
REV
REMOTE/LOCAL switching from the keypad panel
automatically changes the set value from 0 to 3 of this
function.
5-7
or
or
key)
FWD
REV
STOP
key active)
STOP
key inactive)
key active) with GE start
STOP
key inactive) with GE start
STOP
FWD

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents