APPENDIX D
Table D–2: IMPLEMENTATION TABLE (Sheet 4 of 4)
OBJECT
OBJECT
VARIATION
DESCRIPTION
NO.
NO.
34
2
32-bit Analog Input Reporting Deadband
cont'd
3
Short floating point Analog Input Reporting
Deadband
50
0
Time and Date
1
Time and Date
(default – see Note 1)
52
2
Time Delay Fine
60
0
Class 0, 1, 2, and 3 Data
1
Class 0 Data
2
Class 1 Data
3
Class 2 Data
4
Class 3 Data
80
1
Internal Indications
---
No Object (function code only)
see Note 3
---
No Object (function code only)
---
No Object (function code only)
Note 1:
A default variation refers to the variation responded when variation 0 is requested and/or in class 0, 1, 2, or 3 scans. The default varia-
tions for object types 1, 2, 20, 21, 22, 23, 30, and 32 are selected via relay settings. Refer to the Communications section in Chapter 5
for details. This optimizes the class 0 poll data size.
Note 2:
For static (non-change-event) objects, qualifiers 17 or 28 are only responded when a request is sent with qualifiers 17 or 28, respec-
tively. Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change-
event objects, qualifiers 17 or 28 are always responded.)
Note 3:
Cold restarts are implemented the same as warm restarts – the L90 is not restarted, but the DNP process is restarted.
GE Multilin
REQUEST
FUNCTION
QUALIFIER
CODES (DEC)
CODES (HEX)
1
00, 01
(read)
06
(no range, or all)
07, 08
17, 28
2
00, 01
(write)
07, 08
17, 28
1
00, 01
(read)
06
(no range, or all)
07, 08
17, 28
1
00, 01
(read)
06
(no range, or all)
07, 08
17, 28
1
00, 01
(read)
2
06
(write)
(no range, or all)
07
(limited qty=1)
08
(limited quantity)
17, 28
1
06
(read)
(no range, or all)
20
(enable unsol)
21
(disable unsol)
22
(assign class)
1
06
(read)
(no range, or all)
22
(assign class)
1
06
(read)
(no range, or all)
20
07, 08
(enable unsol)
21
(disable unsol)
22
(assign class)
1
06
(read)
(no range, or all)
20
07, 08
(enable unsol)
21
(disable unsol)
22
(assign class)
1
06
(read)
(no range, or all)
20
07, 08
(enable unsol)
21
(disable unsol)
22
(assign class)
2
00
(write)
(start-stop)
(index must =7)
13
(cold restart)
14
(warm restart)
23
(delay meas.)
L90 Line Differential Relay
D.1 DNP PROTOCOL
RESPONSE
FUNCTION
QUALIFIER
CODES (DEC)
CODES (HEX)
129
00, 01
(start-stop)
(response)
17, 28
(see Note 2)
(limited quantity)
(index)
(start-stop)
(limited quantity)
(index)
129
00, 01
(start-stop)
(response)
17, 28
(see Note 2)
(limited quantity)
(index)
129
00, 01
(start-stop)
(response)
17, 28
(see Note 2)
(limited quantity)
(index)
129
00, 01
(start-stop)
(response)
17, 28
(see Note 2)
(index)
129
07
(response)
(quantity = 1)
(limited quantity)
(limited quantity)
(limited quantity)
(start-stop)
(index)
(start-stop)
(index)
(start-stop)
(index)
(start-stop)
(index)
D
(limited quantity)
D-7