GE L90 Instruction Manual page 391

Line differential relay ur series
Hide thumbs Also See for L90:
Table of Contents

Advertisement

APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 6 of 41)
ADDR
REGISTER NAME
1E20
...Repeated for module number 3
1E30
...Repeated for module number 4
1E40
...Repeated for module number 5
1E50
...Repeated for module number 6
Source Demand Peaks (Read Only Non-Volatile) (6 modules)
1E80
SRC 1 Demand Ia Max
1E82
SRC 1 Demand Ia Max Date
1E84
SRC 1 Demand Ib Max
1E86
SRC 1 Demand Ib Max Date
1E88
SRC 1 Demand Ic Max
1E8A
SRC 1 Demand Ic Max Date
1E8C
SRC 1 Demand Watt Max
1E8E
SRC 1 Demand Watt Max Date
1E90
SRC 1 Demand Var
1E92
SRC 1 Demand Var Max Date
1E94
SRC 1 Demand Va Max
1E96
SRC 1 Demand Va Max Date
1E98
Reserved (8 items)
1EA0
...Repeated for module number 2
1EC0
...Repeated for module number 3
1EE0
...Repeated for module number 4
1F00
...Repeated for module number 5
1F20
...Repeated for module number 6
Breaker Flashover (Read/Write Setting) (2 modules)
21A6
Breaker 1 Flashover Function
21A7
Breaker 1 Flashover Side 1 Source
21A8
Breaker 1 Flashover Side 2 Source
21A9
Breaker 1 Flashover Status Closed A
21AA
Breaker 1 Flashover Status Closed B
21AB
Breaker 1 Flashover Status Closed C
21AC
Breaker 1 Flashover Voltage Pickup Level
21AD
Breaker 1 Flashover Voltage Difference Pickup Level
21AF
Breaker 1 Flashover Current Pickup Level
21B0
Breaker 1 Flashover Pickup Delay
21B1
Breaker 1 Flashover Supervision Phase A
21B2
Breaker 1 Flashover Supervision Phase B
21B3
Breaker 1 Flashover Supervision Phase C
21B4
Breaker 1 Flashover Block
21B5
Breaker 1 Flashover Events
21B6
Breaker 1 Flashover Target
21B7
Reserved (4 items)
21BB
...Repeated for module number 2
Breaker Arcing Current Actuals (Read Only Non-Volatile) (2 modules)
21E0
Breaker 1 Arcing Current Phase A
21E2
Breaker 1 Arcing Current Phase B
21E4
Breaker 1 Arcing Current Phase C
21E6
Breaker 1 Operating Time Phase A
21E7
Breaker 1 Operating Time Phase B
21E8
Breaker 1 Operating Time Phase C
21E9
Breaker 1 Operating Time
21E6
...Repeated for module number 2
Breaker Arcing Current Commands (Read/Write Command) (2 modules)
2224
Breaker 1 Arcing Current Clear Command
2225
...Repeated for module number 2
GE Multilin
RANGE
0 to 999999.999
0 to 4294967295
0 to 999999.999
0 to 4294967295
0 to 999999.999
0 to 4294967295
0 to 999999.999
0 to 4294967295
0 to 999999.999
0 to 4294967295
0 to 999999.999
0 to 4294967295
---
0 to 1
0 to 5
0 to 6
0 to 65535
0 to 65535
0 to 65535
0 to 1.5
0 to 100000
0 to 1.5
0 to 65.535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 1
0 to 2
---
0 to 99999999
0 to 99999999
0 to 99999999
0 to 99999999
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 1
L90 Line Differential Relay
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
A
0.001
F060
---
1
F050
A
0.001
F060
---
1
F050
A
0.001
F060
---
1
F050
W
0.001
F060
---
1
F050
var
0.001
F060
---
1
F050
VA
0.001
F060
---
1
F050
---
---
F001
---
1
F102
---
1
F167
---
1
F211
---
1
F300
---
1
F300
---
1
F300
pu
0.001
F001
V
1
F060
pu
0.001
F001
s
0.001
F001
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F102
---
1
F109
---
---
F001
2
kA
-cyc
1
F060
2
kA
-cyc
1
F060
2
kA
-cyc
1
F060
2
kA
-cyc
1
F060
ms
1
F001
ms
1
F001
ms
1
F001
ms
1
F001
---
1
F126
DEFAULT
B
0
0
0
0
0
0
0
0
0
0
0
0
0
0 (Disabled)
0 (SRC 1)
0 (None)
0
0
0
850
1000
600
100
0
0
0
0
0 (Disabled)
0 (Self-Reset)
0
0
0
0
0
0
0
0
0
0 (No)
B-13

Advertisement

Table of Contents
loading

Table of Contents