GE L90 Instruction Manual page 242

Line differential relay ur series
Hide thumbs Also See for L90:
Table of Contents

Advertisement

5.5 GROUPED ELEMENTS
d) 87L TRIP
!"
PATH: SETTINGS
GROUPED ELEMENTS
# 87L TRIP
#
5
The 87L Trip element must be used to secure the generation of tripping outputs. It is especially recommended for use in all
single-pole tripping applications. It provides the user with the capability of maintaining the trip signal while the fault current
is still flowing, to choose single-pole or three-pole tripping, to employ the received Direct Transfer Trip signals, to assign
supervising trip elements like 50DD, etc. The logic is used to ensure that the relay will:
trip the faulted phase for a single line to ground fault, as detected by the line differential element
trip all three phases for any internal multiphase fault
trip all three phases for a second single line to ground fault during or following a single pole trip cycle
For maximum security, it is recommended the Disturbance Detector (plus other elements if required) be assigned to see a
change in system status before a trip output is permitted. This ensures the relay will not issue a trip signal as a result of
incorrect settings, incorrect manipulations with a relay, or inter-relay communications problems (for example, extremely
noisy channels). The Open Pole Detector provides forcing of three-pole tripping for sequential faults and close-onto-fault if
desired. The Open Pole Detector feature must be employed and adequately programmed for proper operation of this fea-
ture. The
87L TRIP 1P OP
If DTT is not required to cause the 87L Trip scheme to operate, it should be disabled at the remote relay via the
!"
ETTINGS
GROUPED ELEMENTS
menu.
NOTE
TIAL
87L TRIP FUNCTION: This setting is used to enable/disable the element.
87L TRIP SOURCE: This setting is used to assign a source for seal-in function.
87L TRIP MODE: This setting is used to select either three-pole or single-pole mode of operation.
87L TRIP SUPV: This setting is used to assign a trip supervising element. The
mended (the element has to be enabled); otherwise, elements like instantaneous overcurrent, distance, etc. can be
used.
87L TRIP FORCE 3-φ: This setting is used to select an element forcing 3-pole tripping if any type fault occurs when
this element is active. Autoreclosure Disabled can be utilized, or Autoreclosure Counter if second trip for example is
required to be a 3-pole signal, or element representing change in the power system configuration, etc. can be consid-
ered to be applied.
5-152
!"
SETTING GROUP 1(6)
87L TRIP FUNCTION:
Disabled
87L TRIP SOURCE:
MESSAGE
SRC 1
87L TRIP MODE:
MESSAGE
3-Pole
87L TRIP SUPV:
MESSAGE
Off
87L TRIP FORCE 3-φ:
MESSAGE
Off
87L TRIP SEAL-IN:
MESSAGE
Disabled
87L TRIP SEAL-IN
MESSAGE
PICKUP: 0.20 pu
87L TRIP TARGET:
MESSAGE
Self-reset
87L TRIP EVENTS:
MESSAGE
Disabled
and
operands are provided to initiate single-pole or three-pole autoreclosing.
87L TRIP 3P OP
!
SETTING GROUP 1(6)
L90 Line Differential Relay
!"
SUPERVISING ELEMENTS
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4
Range: 3-Pole, 1-Pole
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: Disabled, Enabled
Range: 0.20 to 0.80 pu in steps of 0.01
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
!"
LINE DIFFERENTIAL ELEMENTS
FlexLogic™ operand is recom-
50DD SV
5 SETTINGS
!"
87L TRIP
!"
CURRENT DIFFEREN-
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents