5 SETTINGS
CT FAIL 3I0 INPUT 2 PICKUP: This setting is used to select the pickup value for 3I_0 for the Input 2 (different CT
input) of the relay.
CT FAIL 3V0 INPUT: This setting is used to select the source for the voltage.
CT FAIL 3V0 INPUT PICKUP: This setting is used to select the pickup value for 3V_0 source.
CT FAIL PICKUP DELAY: This setting is used to select the pickup delay of the element.
SETTING
CT FAIL FUNCTION:
Disabled=0
Enabled=1
SETTING
CT FAIL BLOCK:
Off=0
SETTING
CT FAIL 3IO INPUT1:
SRC1
SETTING
CT FAIL 3IO INPUT2:
SRC2
SETTING
CT FAIL 3VO INPUT:
SRC1
GE Multilin
SETTING
CT FAIL 3IO INPUT1 PKP:
RUN
3IO > PICKUP
SETTING
CT FAIL 3IO INPUT2 PKP:
RUN
3IO > PICKUP
SETTING
OR
CT FAIL 3VO INPUT:
RUN
3VO > PICKUP
Figure 5–107: CT FAILURE DETECTOR SCHEME LOGIC
L90 Line Differential Relay
SETTING
CT FAIL PICKUP DELAY:
FLEXLOGIC OPERANDS
AND
0
CT FAIL OP
CT FAIL PKP
5.6 CONTROL ELEMENTS
827048A6.CDR
5-177