Follow this manual and precautions when handling the inverter.
Incorrect handling could lead to inhibited operation or a drop operating
life. In the worst case, the inverter could be damaged.
Power supply
Circuit breaker
MCCB
Magnet
contactor
MC
Power factor
improvement
reactor
Input noise
N F
filter
Inverter
Thermal relay
for open phase
protection
8

Points for Handling

Use within + 10%, -15% of the tolerable input
voltage range, and within
input frequency range.
Size a breaker from the selection table on page 17.
A magnet contactor is not required in normal
use. If installed, do not start or stop the inverter
with the magnet contactor.
Connect this when the power factor must be
improved.
Connect this when noise to the peripheral
devices is a problem.
The ambient temperature is the most important
factor for the installation site. Make sure that the
tolerable value is not exceeded.
(See page 9 and 11)
The thermal component built into the inverter is
used to protect against overloads. Use an open
phase protection thermal relay for open phase
protection.
Motor
3-phase induction motor.
5% of the tolerable

Hide quick links: