 Do not bunch the control wires or communication cables with the main circuit or
power wires, or install them close to each other.
They should be installed 100mm (3.94inch) or more from each other.
Not doing so could result in noise that would cause erroneous operation.
 At power ON/OFF, voltage or current may instantaneously be output from the output
terminal of this module.
In such case, wait until the analog output becomes stable to start controlling the
external device.
[Installation Precautions]
 Use the programmable controller in an environment that meets the general
specifications in this manual. Failure to do so may result in electric shock, fire,
malfunction, or damage to or deterioration of the product.
 For protection of the switches, do not remove the cushioning material before
installation.
 Securely fix the module with a DIN rail or mounting screws. Tighten the screws within
the specified torque range.
Undertightening can cause drop of the screw, short circuit, or malfunction.
Overtightening can damage the screw and/or module, resulting in drop, short circuit,
or malfunction.
 Do not directly touch the module's conductive parts or electronic components.
Touching the conductive parts could cause an operation failure or give damage to the
module.
[Wiring Precautions]
 Be sure to shut off all phases of the external power supply used by the system before
installation or wiring.
Not doing so can cause the product to be damaged or malfunction.
 Be sure to ground the FG terminals to the protective ground conductor. Not doing so
could result in erroneous operation.
 Use applicable solderless terminals and tighten them with the specified torque. If any
solderless spade terminal is used, it may be disconnected when the terminal screw
comes loose, resulting in failure.
 When wiring in the programmable controller, be sure that it is done correctly by
checking the product's rated voltage and the terminal layout.
Connecting a power supply that is different from the rating or incorrectly wiring the
product could result in fire or damage.