Before Installation

Check for external damage. If damage exists, immediately document, contact the shipper
and contact ABB.
Delivery Check
The drive delivery contains:
• Drive cabinet including factory installed options such as optional modules
(inserted onto the RMIO board in the RDCU unit)
• Residual voltage warning stickers
• Hardware manual
• Appropriate firmware manuals and guides
• Appropriate optional module manuals
• Delivery documents.
Check that there are no signs of damage. Before attempting installation and
operation, check the information on the type designation label of the drive to verify
that the unit is of the correct type. The label includes a NEMA rating, a type code and
a serial number which allow individual recognition of each unit. The first digit of the
serial number refers to the manufacturing plant. The next four digits refer to the unit's
manufacturing year and week respectively. The remaining digits complete the serial
number so that there are no two units with the same serial number.
The type designation label is located on the inside of the front cover. UL and cUL
listing marks are shown on a seperate label.
Input
Voltage(U1)
Current(I1n)
Short Circuit
Output
Voltage(U2)
Current(I2n)
Power(Pn)
Schematic: 3AUA0000011083
ACS800-PC-0400-5+B055+K454+L503+L504+L505+M603
Requirements for the Installation Site
Check the installation site according to the requirements below. Refer to
ACS800-PC Dimensional Drawings for frame details. See "Technical Data" for the
allowed operation conditions of the drive.
Mechanical Installation
3PH 48...63Hz
380..500 Vac
498 A
100kA
3PH 0...300 Hz
0...U1 Vac
515 A
400 Hp
Type designation label
ABB Inc.
Made in USA of foreign parts
Mfg. Date: 06-August-2008
Orig. Firmware: ASXR734U
S/N 2083201813