Losses, Cooling Data And Noise; Terminal And Lead-Through Data For The Power Cables; Drive Modules Without Output Cable Connection Terminals (+0H371) And With A Common Mode Filter (+E208); Terminal Data For The Control Cables - ABB ACS580-04 Hardware Manual

Drive modules (200 to 500 kw)
Hide thumbs Also See for ACS580-04:
Table of Contents

Advertisement

Losses, cooling data and noise

Drive type
ACS580-505A-4
ACS580-585A-4
ACS580-650A-4
ACS580-725A-4
ACS580-820A-4
ACS580-880A-4

Terminal and lead-through data for the power cables

The maximum accepted cable size is 4 × (3 × 240) mm
for connecting busbars to the drive module input and output busbars: M12, tightening
torque 50...75 N·m.
Drive modules without output cable connection terminals (+0H371)
and with a common mode filter (+E208)
It is possible to use the maximum cable size (4 × [3 × 240] mm
with special cable lugs and additional insulation. For more information, contact your local
ABB representative.

Terminal data for the control cables

See page 82.

Electrical power network specification

Voltage (U
)
1
Network type
Rated conditional short-
circuit current I
(IEC
cc
61439-1)
Short-circuit current
protection (UL 508A)
Frequency
Imbalance
Fundamental power factor
(cos phi
)
1

Motor connection data

Motor types
Voltage (U
)
2
Frequency
Frequency resolution
Current
Frequency
Switching frequency
Frame size
m
R10
1200
R10
1200
R10
1200
R11
1200
R11
1200
R11
1420
380...480 V AC 3-phase ± 10%. This is indicated in the type designation label
as typical input voltage levels 3
TN (grounded) and IT (ungrounded) systems
Maximum allowable prospective short-circuit current is 65 kA when protected
by the fuses given in the fuse table.
The drive is suitable for use on a circuit capable of delivering not more than
100,000 rms symmetrical amperes at 600 V maximum when by the fuses
given in the fuse table.
48 to 63 Hz, maximum rate of change 17%/s
Max. ± 3% of nominal phase to phase input voltage
0.98 (at nominal load)
Asynchronous AC induction motors and permanent magnet motors
0 to U
, 3-phase symmetrical. This is indicated in the type designation label
1
as typical output voltage level 3
0....500 Hz
0.01 Hz
See section
Ratings.
0...500 Hz. For drives with du/dt filter: 200 Hz
= nominal switching frequency. Minimum switching frequency 1.5 kHz, 2 kHz,
4 kHz, 8 kHz (depends on the parameter settings)
Air flow
3
3
/h
ft
/min
707
707
707
707
707
848
2
or 4 × (3 × 500 AWG). Screw size
400/480 V AC.
0...U
,
1
Technical data 117
Heat dissipation
W
5602
6409
8122
8764
9862
10578
3AXD00000586715
2
or 4 ×[(3 × 500 AWG]) only
Noise
dB(A)
72
72
72
72
72
71