B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 53 of 54)
ADDR
REGISTER NAME
EB05
PMU 1 Frequency Trigger Block (3 items)
EB08
PMU 1 Frequency Trigger Target
EB09
PMU 1 Frequency Trigger Events
EB0A
...Repeated for PMU 2
EB14
...Repeated for PMU 3
B
EB1E
...Repeated for PMU 4
Phasor Measurement Unit Power Trigger (Read/Write Setting)
EB28
PMU 1 Power Trigger Function
EB29
PMU 1 Power Trigger Active
EB2A
PMU 1 Power Trigger Reactive
EB2B
PMU 1 Power Trigger Apparent
EB2C
PMU 1 Power Trigger Pickup Time
EB2D
PMU 1 Power Trigger Dropout Time
EB2E
PMU 1 Power Trigger Block (3 items)
EB31
PMU 1 Power Trigger Target
EB32
PMU 1 Power Trigger Events
EB33
...Repeated for PMU 2
EB3E
...Repeated for PMU 3
EB49
...Repeated for PMU 4
Phasor Measurement Unit Voltage Trigger (Read/Write Setting)
EB54
PMU 1 Voltage Trigger Function
EB55
PMU 1 Voltage Trigger Low Voltage
EB56
PMU 1 Voltage Trigger High Voltage
EB57
PMU 1 Voltage Trigger Pickup Time
EB58
PMU 1 Voltage Trigger Dropout Time
EB59
PMU 1 Voltage Trigger Block (3 items)
EB5C
PMU 1 Voltage Trigger Target
EB5D
PMU 1 Voltage Trigger Events
EB5E
...Repeated for PMU 2
EB68
...Repeated for PMU 3
EB72
...Repeated for PMU 4
Phasor Measurement Unit Network Reporting Configuration (Read/Write Setting)
EB7C
PMU Network Reporting Function
EB7D
PMU Network Reporting ID Code
EB7E
PMU Network Reporting Rate
EB7F
PMU Network Reporting Style
EB80
PMU Network Reporting Format
EB81
PMU Network PDC Control
Phasor Measurement Unit One-shot Command (Read/Write Setting)
EB82
PMU One-shot Function
EB83
PMU One-shot Sequence Number
EB84
PMU One-shot Time
Phasor Measurement Unit Test Values (Read/Write Setting)
EB86
PMU 1 Test Function
EB87
PMU 1 Phase A Voltage Test Magnitude
EB89
PMU 1 Phase A Voltage Test Angle
EB8A
PMU 1 Phase B Voltage Test Magnitude
EB8C
PMU 1 Phase B Voltage Test Angle
EB8D
PMU 1 Phase C Voltage Test Magnitude
EB8F
PMU 1 Phase C Voltage Test Angle
EB90
PMU 1 Auxiliary Voltage Test Magnitude
EB92
PMU 1 Auxiliary Voltage Test Angle
EB93
PMU 1 Phase A Current Test Magnitude
EB95
PMU 1 Phase A Current Test Angle
B-60
N60 Network Stability and Synchrophasor Measurement System
RANGE
UNITS
STEP
0 to 65535
---
1
0 to 2
---
1
0 to 1
---
1
0 to 1
---
1
0.25 to 3
pu
0.001
0.25 to 3
pu
0.001
0.25 to 3
pu
0.001
0 to 600
s
0.01
0 to 600
s
0.01
0 to 65535
---
1
0 to 2
---
1
0 to 1
---
1
0 to 1
---
1
0.25 to 1.25
pu
0.001
0.75 to 1.75
pu
0.001
0 to 600
s
0.01
0 to 600
s
0.01
0 to 65535
---
1
0 to 2
---
1
0 to 1
---
1
0 to 1
---
1
1 to 65534
---
1
0 to 10
---
1
0 to 1
---
1
0 to 1
---
1
0 to 1
---
1
0 to 1
---
1
0 to 59
---
1
0 to 235959
---
1
0 to 1
---
1
0 to 700
kV
0.01
-180 to 180
°
0.05
0 to 700
kV
0.01
-180 to 180
°
0.05
0 to 700
kV
0.01
-180 to 180
°
0.05
0 to 700
kV
0.01
-180 to 180
°
0.05
0 to 9.999
kA
0.001
-180 to 180
°
0.05
APPENDIX B
FORMAT
DEFAULT
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
F102
0 (Disabled)
F001
1250
F001
1250
F001
1250
F001
10
F001
100
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
F102
0 (Disabled)
F001
800
F001
1200
F001
10
F001
100
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
F102
0 (Disabled)
F001
1
F544
3 (10/sec.)
F546
0 (Polar)
F547
0 (Integer)
F102
0 (Disabled)
F102
0 (Disabled)
F001
1
F050
0
F102
0 (Disabled)
F003
50000
F002
0
F003
50000
F002
-120
F003
50000
F002
120
F003
50000
F002
0
F004
1000
F002
-10
GE Multilin