GE N60 UR Series Instruction Manual page 416

Network stability and synchrophasor measurement system
Table of Contents

Advertisement

B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 51 of 54)
ADDR
REGISTER NAME
D3FC
...Repeated for Remote Device 32
Phasor Measurement Unit Communication (Read/Write Setting)
D400
PMU 1 Communication Port 1 Type
D401
PMU 1 Communication Port 2 Type
D402
PMU 1 Communication Port 3 Type
B
D403
PMU 1 Port 1 PHS-x (14 items)
D411
PMU 1 Port 2 PHS-x (14 items)
D41F
PMU 1 Port 3 PHS-x (14 items)
D42D
PMU 1 Communication Port 1 PHS-x Name (14 items)
D49D
PMU 1 Port 2 PHS-x Name (14 items)
D50D
PMU 1 Port 3 PHS-x Name (14 items)
D57D
PMU 1 Port 1 A-CH-x (8 items)
D585
PMU 1 Port 2 A-CH-x (8 items)
D58D
PMU 1 Port 3 A-CH-x (8 items)
D595
PMU 1 Port 1 A-CH-x Name (8 items)
D5D5
PMU 1 Port 2 A-CH-x Name (8 items)
D615
PMU 1 Port 3 A-CH-x Name (8 items)
D655
PMU 1 Port 1 D-CH-x (16 items)
D665
PMU 1 Port 2 D-CH-x (16 items)
D675
PMU 1 Port 3 D-CH-x (16 items)
D685
PMU 1 Port 1 D-CH-x Name (16 items)
D705
PMU 1 Port 2 D-CH-x Name (16 items)
D785
PMU 1 Port 3 D-CH-x Name (16 items)
D705
PMU 1 Port 1 D-CH-x Normal State (16 items)
D715
PMU 1 Port 2 D-CH-x Normal State (16 items)
D725
PMU 1 Port 3 D-CH-x Normal State (16 items)
D835
...Repeated for PMU 2
DC6A
...Repeated for PMU 3
E09F
...Repeated for PMU 4
Phasor Measurement Unit Recording Command (Read/Write Command)
E4D4
PMU 1 Recording Clear Command
E4D5
PMU 1 Recording Force Trigger
E4D6
...Repeated for PMU 2
E4D8
...Repeated for PMU 3
E4DA
...Repeated for PMU 4
Phasor Measurement Unit Recording (Read/Write Setting)
E4DC
PMU 1 Recording Rate
E4DD
Reserved
E4DE
PMU 1 No Of Timed Records
E4DF
PMU 1 Trigger Mode
E4E0
PMU 1 Timed Trigger Position
E4E1
Reserved
E4E2
PMU 1 Record PHS-1 (14 items)
E4F0
PMU 1 Record PHS-x Name (14 items)
E560
PMU 1 Record A-CH-x (8 items)
E568
PMU 1 Record A-CH-x Name (8 items)
E5A8
PMU 1 Record D-CH-x (16 items)
E5B8
PMU 1 Record D-CH-x Name (16 items)
E638
...Repeated for PMU 2
E794
...Repeated for PMU 3
E8F0
...Repeated for PMU 4
Phasor Measurement Unit Basic Configuration (Read/Write Setting)
EA58
PMU 1 Function
EA59
PMU 1 IDcode
B-58
N60 Network Stability and Synchrophasor Measurement System
RANGE
UNITS
STEP
0 to 3
---
1
0 to 3
---
1
0 to 3
---
1
0 to 14
---
1
0 to 14
---
1
0 to 14
---
1
---
---
---
---
---
---
---
---
---
0 to 65535
---
1
0 to 65535
---
1
0 to 65535
---
1
---
---
---
---
---
---
---
---
---
0 to 65535
---
1
0 to 65535
---
1
0 to 65535
---
1
---
---
---
---
---
---
---
---
---
0 to 1
---
1
0 to 1
---
1
0 to 1
---
1
0 to 1
---
1
0 to 1
---
1
0 to 10
---
1
---
---
1
1 to 128
---
1
0 to 1
---
1
1 to 50
%
1
---
---
1
0 to 14
---
1
---
---
---
0 to 65535
---
1
---
---
---
0 to 65535
---
1
---
---
---
0 to 1
---
1
1 to 65534
---
1
APPENDIX B
FORMAT
DEFAULT
F545
0 (Network)
F545
0 (Network)
F545
0 (Network)
F543
1 (Va)
F543
1 (Va)
F543
1 (Va)
F203
"GE-UR-PMU-PHS 1"
F203
"GE-UR-PMU-PHS 1"
F203
"GE-UR-PMU-PHS 1"
F600
0
F600
0
F600
0
F203
"AnalogChannel 1"
F203
"AnalogChannel 1"
F203
"AnalogChannel 1"
F300
0
F300
0
F300
0
F203
"Dig Channel 1"
F203
"Dig Channel 1"
F203
"Dig Channel 1"
F108
0 (Off)
F108
0 (Off)
F108
0 (Off)
F126
0 (No)
F126
0 (No)
F544
3 (10/sec.)
F001
0
F001
3
F542
0 (Auto Overwrite)
F001
10
F001
0
F543
1 (Va)
F203
GE-UR-PMU-PHS 1
F600
0
F203
AnalogChannel 1
F300
0
F203
Dig Channel 1
F102
0 (Disabled)
F001
1
GE Multilin

Advertisement