GE N60 UR Series Instruction Manual page 417

Network stability and synchrophasor measurement system
Table of Contents

Advertisement

APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 52 of 54)
ADDR
REGISTER NAME
EA5A
PMU 1 STN
EA62
PMU 1 Source
EA63
PMU 1 Post-Filter
EA64
...Repeated for PMU 2
EA70
...Repeated for PMU 3
EA7C
...Repeated for PMU 4
Phasor Measurement Unit Calibration (Read/Write Setting)
EA88
PMU 1 Va Calibration Angle
EA89
PMU 1 Vb Calibration Angle
EA8A
PMU 1 Vc Calibration Angle
EA8B
PMU 1 Vx Calibration Angle
EA8C
PMU 1 Ia Calibration Angle
EA8D
PMU 1 Ib Calibration Angle
EA8E
PMU 1 Ic Calibration Angle
EA8F
PMU 1 Ig Calibration Angle
EA90
PMU 1 Sequence Voltage Shift Angle
EA91
PMU 1 Sequence Current Shift Angle
EA92
...Repeated for PMU 2
EA9C
...Repeated for PMU 3
EAA6
...Repeated for PMU 4
Phasor Measurement Unit Triggering (Read/Write Setting)
EAB0
PMU 1 User Trigger
EAB1
...Repeated for PMU 2
EAB2
...Repeated for PMU 3
EAB3
...Repeated for PMU 4
Phasor Measurement Unit Current Trigger (Read/Write Setting)
EAB4
PMU 1 Current Trigger Function
EAB5
PMU 1 Current Trigger Pickup
EAB6
PMU 1 Current Trigger Pickup Time
EAB7
PMU 1 Current Trigger Dropout Time
EAB8
PMU 1 Current Trigger Block (3 items)
EABB
PMU 1 Current Trigger Target
EABC
PMU 1 Current Trigger Events
EABD
...Repeated for PMU 2
EAC6
...Repeated for PMU 3
EACF
...Repeated for PMU 4
Phasor Measurement Unit df/dt Trigger (Read/Write Setting)
EAD8
PMU 1 df/dt Trigger Function
EAD9
PMU 1 df/dt Trigger Raise
EADA
PMU 1 df/dt Trigger Fall
EADB
PMU 1 df/dt Trigger Pickup Time
EADC
PMU 1 df/dt Trigger Dropout Time
EADD
PMU 1 df/dt Trigger Block (3 items)
EAE0
PMU 1 df/dt Trigger Target
EAE1
PMU 1 df/dt Trigger Events
EAE2
...Repeated for PMU 2
EAEC
...Repeated for PMU 3
EAF6
...Repeated for PMU 4
Phasor Measurement Unit Frequency Trigger (Read/Write Setting)
EB00
PMU 1 Frequency Trigger Function
EB01
PMU 1 Frequency Trigger Low Frequency
EB02
PMU 1 Frequency Trigger High Frequency
EB03
PMU 1 Frequency Trigger Pickup Time
EB04
PMU 1 Frequency Trigger Dropout Time
GE Multilin
N60 Network Stability and Synchrophasor Measurement System
RANGE
UNITS
STEP
---
---
---
0 to 5
---
1
0 to 3
---
1
-5 to 5
°
0.05
-5 to 5
°
0.05
-5 to 5
°
0.05
-5 to 5
°
0.05
-5 to 5
°
0.05
-5 to 5
°
0.05
-5 to 5
°
0.05
-5 to 5
°
0.05
-180 to 180
°
30
-180 to 180
°
30
0 to 65535
---
1
0 to 1
---
1
0.1 to 30
pu
0.001
0 to 600
s
0.01
0 to 600
s
0.01
0 to 65535
---
1
0 to 2
---
1
0 to 1
---
1
0 to 1
---
1
0.1 to 15
Hz/s
0.01
0.1 to 15
Hz/s
0.01
0 to 600
s
0.01
0 to 600
s
0.01
0 to 65535
---
1
0 to 2
---
1
0 to 1
---
1
0 to 1
---
1
20 to 70
Hz
0.01
20 to 70
Hz
0.01
0 to 600
s
0.01
0 to 600
s
0.01
B.4 MEMORY MAPPING
FORMAT
DEFAULT
F203
"GE-UR-PMU"
F167
0 (SRC 1)
F540
1 (Symm-3-point)
F002
0
F002
0
F002
0
F002
0
F002
0
F002
0
F002
0
F002
0
F002
0
F002
0
F300
0
F102
0 (Disabled)
F001
1800
F001
10
F001
100
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
F102
0 (Disabled)
F001
25
F001
25
F001
10
F001
100
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
F102
0 (Disabled)
F001
4900
F001
6100
F001
10
F001
100
B-59
B

Advertisement

Table of Contents
loading

Table of Contents