6-42. How to Install the Ceiling Panel
(1) Removing the air-intake grille
1) Remove the 2 screws on the latch of the air-intake grille.
(Fig. 1-131) (Reattach the air-intake grille after installation
of the ceiling panel.)
2) Slide the air-intake grille catches in the direction shown by
the arrows 1 to open the grille. (Fig. 1-131)
Air-intake grille
Ceiling panel
1
1
Air-intake
grille hinge
3) With the air-intake grille opened, remove the grille hinge
from the ceiling panel by sliding it in the direction shown
by the arrow 2. (Fig. 1-132) (Reattach the air-intake grille
after installation of the ceiling panel.)
2
(2) Removing the corner cover
Slide the corner cover in the direction of the arrow 1 and
remove it.
Corner cover
Corner cover
2
Slide
Strap
Screw
Latch
Fig. 1-131
Fig. 1-132
1
Push to
disengage
Ceiling panel
Fig. 1-133
(3) Installing the ceiling panel
The power must be turned ON in order to change the flap angle. (Do
not attempt to move the flap by hand. Doing so may damage the flap.)
1) Hang the temporary latches on the inside of the ceiling panel to
the receptacle on the unit to temporarily attach the ceiling panel
in place. (Fig. 1-134)
The ceiling panel must be installed in the correct direction
relative to the unit. Align the REF. PIPE and DRAIN marks on the
ceiling panel corner with the correct positions on the unit.
When removing the ceiling panel, push the temporary latches
outward while holding the ceiling panel.
(Fig. 1-134)
Push to disengage
Temporary latch
2) Align the panel installation holes and the unit screw holes.
3) Tighten the supplied washer head screws at the 4 panel
installation locations so that the panel is attached tightly to the
unit. (Fig. 1-135)
Ceiling panel
4) Check that the panel is attached tightly to the ceiling.
At this time, make sure that there are no gaps between
the unit and the ceiling panel, or between the ceiling panel
and the ceiling surface. (Fig. 1-136)
Ceiling surface
If there is a gap between the panel and the ceiling, leave the ceiling
panel attached and make fine adjustments to the installation height
of the unit to eliminate the gap with the ceiling. (Fig. 1-137)
1-155
1. Specifications
Receptacle on the
main unit
Temporary latch
Fig. 1-134
Drain tube corner
Refrigerant tube
corner
DRAIN mark
REF. mark
Washer head screws
Fig. 1-135
Do not allow gaps.
Main unit
Ceiling panel
Fig. 1-136
Make fine adjustments by a wrench or
other tool to the installation height of the
unit to eliminate the gap with the ceiling
through the hole of the corner cover.
Fig. 1-137