Mitsubishi Electric FR-A800 Installation Manuallines page 61

Hide thumbs Also See for FR-A800:
Table of Contents

Advertisement

8.1.3 FR-A842 (400V class)
Model FR-A842-
SLD
Applicable motor capacity
LD
*1
[kW]
ND (initial setting)
HD
SLD
LD
*2
Rated capacity [kVA]
ND (initial setting)
HD
SLD
LD
Rated current [A]
ND (initial setting)
HD
SLD
LD
*3
Overload current rating
ND (initial setting)
HD
*4
Rated voltage
Regenerative braking torque
Maximum brake
*5
(when the converter unit
torque
FR-CC2 is used)
Control power supply auxiliary input
DC power supply voltage
Permissible control power supply auxiliary input
fluctuation
*6
Protective structure (IEC 60529)
Cooling system
Weight [kg]
*1
The applicable motor capacity indicated is the maximum capacity applicable for use of the Mitsubishi 4-pole standard motor.
*2
The rated output capacity indicated assumes that the output voltage is 440V.
*3
The % value of the overload current rating indicated is the ratio of the overload current to the inverter's rated output current. For repeated duty, allow time
for the inverter and motor to return to or below the temperatures under 100% load.
*4
The maximum output voltage does not exceed the power supply voltage. The maximum output voltage can be changed within the setting range. However,
the maximum point of the voltage waveform at the inverter output side is the power supply voltage multiplied by about √2.
*5
Value for the ND rating
*6
FR-DU08: IP40 (except for the PU connector section)
*7
For the power voltage exceeding 480V, set Pr. 977 "Input voltage mode selection". (For details, refer to the FR-A800 Instruction Manual.)
For ratings of the converter unit (FR-CC2) refer to the FR-CC2 Instruction Manual.
8.1.4 FR-A846 (400V class)
Model FR-A846-
Applicable motor capacity
LD
*1
[kW]
ND (initial setting)
LD
*2
Rated capacity [kVA]
ND (initial setting)
LD
Rated current [A]
ND (initial setting)
LD
*3
Overload current rating
ND (initial setting)
*4
Rated voltage
Maximum brake
Regenerative braking
torque
Rated input AC voltage/frequency
Permissible AC voltage fluctuation
Permissible frequency fluctuation
LD
*6
Rated input current [A]
ND (initial setting)
Power supply capacity
LD
*7
[kVA]
ND (initial setting)
IEC 60529
*9
Protective structure
UL50
Cooling system
Weight [kg]
*1
The applicable motor capacity indicated is the maximum capacity applicable for use of the Mitsubishi 4-pole standard motor.
*2
The rated output capacity indicated assumes that the output voltage is 440V.
*3
The % value of the overload current rating indicated is the ratio of the overload current to the inverter's rated output current. For repeated duty, allow time
for the inverter and motor to return to or below the temperatures under 100% load.
*4
The maximum output voltage does not exceed the power supply voltage. The maximum output voltage can be changed within the setting range. However,
the maximum point of the voltage waveform at the inverter output side is the power supply voltage multiplied by about √2.
*5
Value for the ND rating
*6
The rated input current indicates a value at a rated output voltage. The impedance at the power supply side (including those of the input reactor and
cables) affects the rated input current.
*7
The power supply capacity is the value when at the rated output current. It varies by the impedance at the power supply side (including those of the input
reactor and cables).
*8
For the power voltage exceeding 480V, set Pr. 977 "Input voltage mode selection". (For details, refer to the Instruction Manual.)
*9
UL Type 12 Enclosure-Suitable for Installation in a Compartment Handling Conditioned Air (Plenum)
*10
For compliance with IP55, remove the protective bushes and install the recommended cable glands.
07700
(315K)
400
355
315
280
587
521
465
417
770
683
610
547
110% of rated motor capacity for 60s, 120% of rated motor capacity for 3s (max. surrounding air temperature 40°C)
120% of rated motor capacity for 60s, 150% of rated motor capacity for 3s (max. surrounding air temperature 50°C)
150% of rated motor capacity for 60s, 200% of rated motor capacity for 3s (max. surrounding air temperature 50°C)
200% of rated motor capacity for 60s, 250% of rated motor capacity for 3s (max. surrounding air temperature 50°C)
Three-phase 380 to 500V
10% torque/continuous
Single-phase 380 to 500V 50Hz/60Hz
430 to 780VDC
Frequency ±5%, voltage ±10%
IP00
Forced air cooling
163
00023
00038
(0.4K)
(0.75K)
0.75
1.5
2.2
0.4
0.75
1.5
1.6
2.7
3.7
1.1
1.9
3
2.1
3.5
4.8
1.5
2.5
4
120% of rated motor capacity for 60s, 150% of rated motor capacity for 3s (max. surrounding air temperature 40°C)
150% of rated motor capacity for 60s, 200% of rated motor capacity for 3s (max. surrounding air temperature 40°C)
Three-phase 380 to 500V
10% torque/continuous
*5
Three-phase 380 to 500V 50Hz/60Hz
323 to 550V 50Hz/60Hz
±5%
2.1
3.5
4.8
1.5
2.5
4
1.6
2.7
3.7
1.1
1.9
3
Dust- and water-proof type (IP55)
*9
UL Type12
Self-cooling + internal fan
15
15
15
08660
09620
(355K)
(400K)
450
500
400
450
355
400
315
355
660
733
587
660
521
587
465
521
866
962
770
866
683
770
610
683
*7
163
243
00052
00083
00126
00170
(1.5K)
(2.2K)
(3.7K)
(5.5K)
3.7
5.5
7.5
2.2
3.7
5.5
5.8
8.8
12
4.6
6.9
9.1
7.6
11.5
16
6
9
12
*8
7.6
11.5
16
6
9
12
5.8
9
12
4.6
6.9
9
*10
15
16
17
SPECIFICATIONS
10940
12120
(450K)
(500K)
500
450
500
400
450
834
924
733
834
660
733
587
660
1094
1212
962
1094
866
962
770
866
243
243
00250
00310
00380
(7.5K)
(11K)
(15K)
11
15
18.5
22
7.5
11
15
18.5
18
22
27
33
13
18
24
29
23
29
35
43
17
23
31
38
23
29
35
43
17
23
31
38
18
22
27
33
13
18
24
29
Forced air cooling + internal fan
26
26
27
27
00470
(18.5K)
55