Mitsubishi Electric FR-A800 Installation Manuallines page 14

Hide thumbs Also See for FR-A800:
Table of Contents

Advertisement

WIRING
*1
For the FR-A820-03800(75K) or higher and FR-A840-02160(75K) or higher, or if using a motor with a capacity of 75 kW or higher,
always connect a DC reactor (FR-HEL), which is available as an option.
(When selecting a DC reactor, refer to page 53, and select one suitable for the applicable motor capacity.) When a DC reactor is
connected to the FR-A820-03160(55K) or lower or the FR-A840-01800(55K) or lower, if a jumper is installed across the terminals P1
and P/+, remove the jumper before installing the DC reactor.
*2
When using separate power supply for the control circuit, remove the jumper between R1/L11 and S1/L21.
*3
The function of these terminals can be changed with the input terminal assignment (Pr. 178 to Pr. 189). (Refer to page 33.)
*4
Terminal JOG is also used as the pulse train input terminal. Use Pr. 291 to choose JOG or pulse.
*5
Terminal input specifications can be changed by analog input specification switchover (Pr. 73, Pr. 267). To input a voltage (0 to 5 V/0 to
10 V), set the voltage/current input switch OFF. To input a current (4 to 20 mA), set the voltage/current input switch ON. Terminals 10
and 2 are also used as a PTC input terminal. (Pr. 561) (Refer to the FR-A800 Instruction Manual.)
*6
It is recommended to use 2W, 1kΩ when the frequency setting signal is changed frequently.
*7
If connecting a brake resistor, remove the jumper between PR and PX (FR-A820-00046(0.4K) to 00490(7.5K), FR-A840-00023(0.4K)
to 00250(7.5K)).
*8
The terminal PR is equipped in FR-A820-00046(0.4K) to 01250(22K), FR-A840-00023(0.4K) to 00620(22K). Install a thermal relay to
prevent overheating and damage of discharging resistors. (Refer to the Instruction Manual.)
*9
The function of these terminals can be changed with the output terminal assignment (Pr. 195, Pr. 196). (Refer to page 33.)
*10
The function of these terminals can be changed with the output terminal assignment (Pr. 190 to Pr. 194). (Refer to page 33.)
CAUTION
To prevent a malfunction due to noise, keep the signal cables more than 10cm away from the power cables. Also, separate the main
circuit cables at the input side from the main circuit cables at the output side.
After wiring, wire offcuts must not be left in the inverter.
Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter clean.
When drilling mounting holes in a control box etc., take care not to allow chips and other foreign matter to enter the inverter.
Set the voltage/current input switch in the correct position. An incorrect setting may cause a fault, failure or malfunction.
8