Inverter Status Monitoring, Special Registers
for Control
(5) Parameter clear (D9147)
Writing H9696 or H9966 to D9147 clears all parameters. Writing H5A5A or
H55AA to D9147 clears the parameters other than the communication
parameters (Refer to the Inverter instruction manual (applied)).
Device No.
D9147
At completion of clear, the write completion signal (X27) turns on, and at the
same time, 0 is set to D9150. If any value outside the setting range is written or
write is performed during inverter operation, HFFFF is set to D9150 as soon as
the write completion signal (X27) turns on, resulting in abnormal completion. If
abnormal completion occurs, the parameters are not cleared.
REMARKS
Check the terminal function parameters and communication-related parameters in the
parameter list (Refer to the Inverter instruction manual (applied)).
POINT
Setting is enabled in the PU operation mode and NET operation mode. Refer to
the inverter instruction manual (applied).
<All parameter clear program example>
The following program clears all parameters.
All parameter clear request
Related device
Device D9150: Parameter access error code (refer to page 33)
30
Setting
Description
H9696
All parameter clear
H9966
H5A5A
Parameters other than
communication parameters
H55AA
are cleared.
Terminal functions are not
cleared.
Terminal functions are
cleared.
Terminal functions are not
cleared.
Terminal functions are
cleared.
Turns on all parameter
clear request pulse.
Check whether all parameter
clear signal turned on to judge
Normal write
whether write was performed
normally or not.
Abnormal write
Stores H9696 (all parameter
clear code) to D9146 and turns
on alarm definition batch clear
command.
(Until completion signal turns on)
Details