Mitsubishi Electric 700 Series Programming Manual page 24

700 series plc function programming manual
Hide thumbs Also See for 700 Series:
Table of Contents

Advertisement

Number
Name
Second
D9234
parameter
changing (RAM) When setting the calibration(bias/gain) parameters.
Second
parameter
D9235
changing
(EEPROM)
Pulse train input
D9236
sampling pulse
Pulse train input
D9237
cumulative count
value L
Pulse train input
D9238
cumulative count
value H
Reset request of
D9239
pulse train input
count
Count start of the
D9240
pulse train input
Parameter
D9241
number (RAM)
Parameter
D9242
description
(RAM)
Parameter
D9243
number
(EEPROM)
Parameter
D9244
description
(EEPROM)
D9245
Terminal 1 input
D9246
Terminal 2 input
D9247
Terminal 4 input
PID set point /
D9248
PID deviation
PID
D9249
measurement
value
PID manipulated
D9250
variable
Terminal FM
D9251
output
Terminal AM
D9252
output
D9253
AM0 output
D9254
AM1 output
PID operation
D9255
control
Description
H00: Frequency(toruque)
H01: Parameter-set analog value
H02: Analog value input from terminal
The number of pulses counted in count cycle is
stored. (0 to 32767)
The cumulative value of the number of sampling
pulses is stored. (0 to 99999999)
The sampling pulses and cumulative count value are
cleared. Automatically changes to "0" after reset.
(1: count clear)
Start counting the sampling pulses and cumulative
count value. (0: count stop, 1: count start)
Set the number of parameter read or written of the
inverter.
The parameter description of the inverter (RAM value)
specified by D9241 is stored. Set the parameter
setting for parameter write.
Set the number of parameter read or written of the
inverter.
The parameter description of the inverter (EEPROM
value) specified by D9243 is stored. Set the
parameter setting for parameter write.
Analog input value of terminal 1 (0.1% increments) is
stored.
Analog input value of terminal 2 (0.1% increments) is
stored.
Analog input value of terminal 4 (0.1% increments) is
stored.
Set the PID set point or PID deviation (0.01% units)
Set the PID measurement value (0.01% units)
Stores the PID manipulated variable (0.01% units)
When Pr. 54 is set to "70", pulse train can be output
from terminal FM. High speed pulse train output can
be performed. (0.1% increments)
When Pr. 158 is set to "70", analog output can be
performed from terminal AM. (0.1% increments)
Analog output can be performed from terminal AM0
and AM1 of the FR-A7AY. (0.1% increments)
Setting 1 starts PID control.
Device Map
Page
34, 36
40
34, 36
1
39
41
39
41
19

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-a700