Siemens SITRANS LCS100 Operating Instructions Manual page 39

Capacitance switches
Table of Contents

Advertisement

IO-Link Registers
Process Data (PDE - Process Data Exchange)
Bit 0 (LSB) to Bit 13
(MSB)
Actual measured value:
0 ... 10000
(equates to 0.00% -
100.00%)
In application with overfill approval (WHG, VLAREM II) the use of IO-Link is applicable
for setting parameters only.
The "Process data Exchange" is not allowed, instead the signal output (PNP, NPN) must be
used.
Item
System commands
System
command
System Command 130 sets all stated registers to "Default value", except register 127, which is set to
"1 = IO-Link"
System Command 160 sets registers 96, 97, 112, 113 to "Default values". Register 127 is set to "1 =
IO-Link"
System Command 161 sets register 127 to "0 = Potentiometer"
IO-Link specific device data
Vendor ID
Device ID
Vendor
Name
Product
Name
Product Text 20
Serial num-
ber
Hardware
Revision
Firmware
Revision
Application-
specific Tag
Function Tag 25
SITRANS LCS100 I/O Link Version
Operating Instructions, 05/2023, A5E52382716-AA
Bit 14
Status
Out 1
WARNING
ISDU
Access Length
(dec)
2
W
7-8
R
9-11
R
16
R
18
R
R
21
R
22
R
23
R
24
R/W
R/W
Bit 15
Data Type: uInteger
Status Out 1 and Out 2:
Status
1 = contact
Out 2
closed
0 = contact open
Data
Value Range
(byte)
type
1
UInt
129 = Application Reset
130 = Factory reset
131 = Back-to-box
160 = Reset switchpoints to default
values
161 = Switchpoint setting by poten-
tiometer
2
UInt
4
UInt
64
String
64
String
64
String
64
String
2
String
5
String
32
String
32
String
Operating
6.3 Operation with IO-Link
Pin assignment:
See Output logic
(Page 26).
Default
value
42
725251
Siemens AG
Capacitance
point level
switch
***
***
39