Honeywell SDC Service Manual page 93

Smile sdc heating and district heating controller
Table of Contents

Advertisement

SDC / DHC
Para-
Designation
meter
03
Room connection
(in conjunction
with room sensor)
04
Room factor
07
Heating limit
08
Room frost-
protection limit
09
Room thermostat
function
10
Assignment of
outside sensor
11
Constant
temperature
setpoint
EN2H-0221GE51 R0812
Setting range / Setting values
OFF
Display of heat
generator temperature,
room sensor off,
operation active
1
Display of room
temperature, room sensor
active, operation active
2
Display of room
temperature, room sensor
active, operation
disabled
3
Display of room
temperature, room sensor
off, operation active
OFF
10 ...
Influence active
500
%
RC
Room controller active
OFF, 0.5 to 40 K
5 ... 30°C
OFF, 0.5 to 5 K
0
Regulation to average
value (outside sensor 1
+ outside sensor 2)
1
Regulation to outside
sensor 1
2
Regulation to outside
sensor 2
10 ... 95°C
Operation
Factory
Setting
setting
OFF
OFF
OFF
10
OFF
0
20
93