Operation
5.4.9
Para-
Designation
meter
01
Switch-on
differential
02
Switch-off
differential
03
Minimum runtime
of solar charging
pump
05
Buffer maximum
temperature limit
06
Operating mode
07
Heat generator
cycle inhibitor
(only if parameter
06 = 1)
08
Solar priority
parallel switchover
09
Heat balance
10
Reset heat
balance
11
Volume flow
106

"Solar" menu (SOLAR)

The parameters in this menu refer to special settings with regard
to the solar applications.
Enabling occurs only with corresponding activation in the
"Hydraulics" menu.
Setting range / Setting values
(Setting value of parameter
02 + 3 K) to 30 K
2 K to (setting value of parameter
01 – 3 K)
0 ... 60 min
20 ... 110°C
1
Priority operation
2
Parallel operation
3
Priority operation of hot-
water circuit
4
Priority operation of
buffer
OFF, 0.5 to 24 h
OFF, 1 to 30 K
OFF
No heat balancing
1
Heat balancing via flow-
through calculation
2
Heat balancing via pulse
input
SET by pressing the input button
0 ... 30 L/min or L/pulse
SDC / DHC
Factory
Setting
setting
10
5
3
75
2
OFF
OFF
OFF
0
EN2H-0221GE51 R0812