Solid" Menu (Solid Fuel); Buffer" Menu (Buffer) - Honeywell SDC Service Manual

Smile sdc heating and district heating controller
Table of Contents

Advertisement

SDC / DHC
Para-
Designation
meter
12
Density of medium
13
Heat capacity of
medium
15
Test cycle of solar
charging
switchover
16
Switchover tem-
perature
5.4.10
Para-
Designation
meter
01
Minimum
temperature
02
Maximum
temperature
03
Switch-on
differential
04
Switch-off
differential
05
Heat generator
cycle inhibitor
5.4.11
EN2H-0221GE51 R0812
Setting range / Setting values
0.8 ... 1.2 kg/L
2 ... 5 KJ/kgK
1 ... 60 min
20 ... 110 °C

"Solid" menu (SOLID FUEL)

The parameters in this menu refer to special settings with regard
to solids regulation.
Enabling occurs only with corresponding activation in the
"Hydraulics" menu.
Setting range / Setting values
20 ... 80 °C
30 ... 100 °C
(Setting value of parameter
04 + 3 K) to 20 K
2 K to (setting value of parameter
03 – 3 K)
OFF, 2 to 180 min

"Buffer" menu (BUFFER)

The parameters in this menu refer to special settings with regard
to solids regulation.
Enabling occurs only with corresponding activation in the
"Hydraulics" menu.
Operation
Factory
Setting
setting
1.05
3.6
10
75
Factory
Setting
setting
60
90
10
5
OFF
107

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dhc