Modulation Of Start Power - Honeywell SDC Service Manual

Smile sdc heating and district heating controller
Table of Contents

Advertisement

SDC / DHC
7.1.14
EN2H-0221GE51 R0812

Modulation of start power

The start power parameter determines a percentage setting for
part of the modulation runtime during the start-up phase. With a
setting of 0% the actuator valve remains always closed. As soon
as the set start time has expired, the modulation switches to its
normal control characteristics defined by the modulation
parameters.
a
Modulation
b
Upward/downward modulation
depending on the control deviation
c
Adjustment operation
d
Start-up phase
Hydraulic Components
e
Base load
f
On
g
Start
x
Starting load (%)