Honeywell SDC Service Manual page 104

Smile sdc heating and district heating controller
Table of Contents

Advertisement

Operation
Para-
Designation
meter
01
Increase
02
Maximum limit of
flow temperature
setpoint
03*
Minimum district
heating valve
stroke
04
Secondary flow
boost
05
Adjustment time
06
Runtime of district
heating valve 1
07*
Runtime of district
heating valve 2
08
Maximum return
temperature
setpoint
09
Application point
variable district
heating return
temperature
10
Maximum return
temperature
setpoint with hot
water circuit
charge
104
Setting range / Setting values
OFF, –10 to 50 K
10 ... 130 °C
0 ... 50 %
0,1 ... 30 %/K
0 ... 60 min
10 ... 1800 s
10 ... 1800 s
0 ... 100 °C
OFF, –40 to +10 °C
0 ... 100 °C
SDC / DHC
Factory
Setting
setting
0
90
10
5
3
120
30
90
OFF
90
EN2H-0221GE51 R0812