For Thyro-A 2A (load with joint neutral point without N conductor) the setting for
load monitoring can be made according to the table below:
e.g.
I
load nom.
parallel
/
load
I
type contr.
resistances
Number
1
100%
1
80%
1
60%
-
-

Tab. 2d Load monitoring

Value deviations can be converted by percentage. The set monitoring value must
lie "in the middle" between the nominal load current value and the value after
outage.
NOTE
Settings above 90% and below 10% are not practical. If low load cur-
rents are required, check if a controller with a lower type current can
be used.
In the VAR operating mode monitoring with large trigger delay angles
C
Œ 140°el. is locked.
82
load with joint neutral point without N
Resistance
Recommended
increase
setting
in case of fault
for poti
(L2)
R205
90.0%
72.0%
(54%)
-
-
Thyro-A 2A
X2.9
X2.9 [V]
[0-20mA]
9.0
18.0
7.2
14.4
5.4
10.8
-
-
-
-
ca.
Revo-
lutions
14.0
11.5
9.0
-
-