Setup data setting
No. Item code
Item
1
PV1 range number
C 01
2
PV1 temperature unit
C 02
3
PV1 decimal point position
C 03
4
C 04
PV1 linear decimal point position 1
5
PV1 linear range lower limit
C 05
6
C 06
PV1 linear range upper limit
7
PV1 cold junction compensation
C 07
8
PV1 root extraction
C 08
9
PV1 root extraction dropout
C 09
10 C 10
PV1 cold junction bias
11 C 11
PV2 range number
12 C 12
PV2 temperature unit
13 C 13
PV2 decimal point position
14 C 14
PV2 linear decimal point position 1
15 C 15
PV2 linear range lower limit
16 C 16
PV2 linear range upper limit
17 C 17
PV2 cold junction compensation
18 C 18
PV2 root extraction
19 C 19
PV2 root extraction dropout
20 C 20
PV2 cold junction bias
21 C 21
Control output system (CH1)
22 C 22
Control output system (CH2)
23 C 23
Control action (CH1)
24 C 24
Control action (CH2)
30 C 30
PV equalizer
31 C 31
End of operation (CH1)
32 C 32
Manipulated variable in READY 0.0
mode (CH1)
33 C 33
Manipulated variable setting
in PV overrange (CH1)
Factory default User
settings
settings
0
0 to 16
48 to 52
64 to 71
96 to 103 : Resistance temperature detector
128 to 134 : Linear (DC current and DC voltage)
0
0 : Celsius (°C)
1 : Fahrenheit (°F)
1
0 to 2
0 to 4
0 PVU
–19999 to +20000 PVU(PV1)
10000 PVU
–19999 to +20000 PVU(PV1)
0
0 : Provided (Compensated inside the instrument)
1 : Not provided (Compensated outside the instrument)
0
0 : Not provided
1 : Provided
0.2
0.2 to 10.0% (Ratio to input range)
0.0
–1.0 to + 1.0°C
0
0 to 16
48 to 52
64 to 71
96 to 103 : Resistance temperature detector
128 to 134 : Linear (DC current and DC voltage)
135
0
0 : Celsius (°C)
1 : Fahrenheit (°F)
1
0 to 2
0 to 4
0 PVU
–19999 to +20000 PVU(PV2)
10000 PVU
–19999 to +20000 PVU(PV2)
0
0 : Provided (Compensated inside the instrument)
1 : Not provided (Compensated outside the instrument)
0
0 : Not provided
1 : Provided
0.2
0.2 to 10.0% (Ratio to input range)
0.0
–1.0 to + 1.0°C
1
1 : 5G output (Current proportional control output)
2 : 6D output (Voltage time proportional control output) system A
3 : 6D output (Voltage time proportional control output) system B
4 : 8D output (open collector time proportional control output) system A
5 : 8D output (open collector time proportional control output) system B
1
0
0 : PID — A reverse operation
1 : PID — A normal operation
2 : PID — B reverse operation
3 : PID — B normal operation
0
0
0 : None
1 : PV1 only
2 : PV2 only
3 : Both PV1 and PV2
0
0 : READY mode
1 : END mode
–5.0 to +105.0%
0
0 : No
1 : Yes
DCP552 Parameter Work Sheet
Settings and descriptions
: Thermocouple
: Linear (DC current and DC voltage)
: Resistance temperature detector
: Thermocouple
: Linear (DC current and DC voltage)
: Resistance temperature detector