Chapter 8. PROGRAM SETUP
When the event is a timer code event
Display (Code event with a timer function)
NOTE
8-10
(1) In the set value display state, move to the event item to be set for the segment
on the programming map.
(2) Press the ENTER key to make display panel 1 flash (registration of first
setting).
(3) Use the ↑, ↓, ←, and → keys to make the first setting (output code).
n
Setting range:0 to 2
(n indicates the number of output points set in event
configuration 1 auxiliary setting 1.)
(4) Press the ENTER key to stop the flashing on display panel 1 and display
panel 2 starts flashing. (Start of second setting)
(Pressing the FUNC and CLR keys causes display panel 1 and 2 to return to
unset state "-----" and the flashing stops.)
(5) Use the ↑, ↓, ←, and → keys to make the second setting (time).
Setting range:
0:00 to 500:00, 0.0 to 3000.0
(Time units are selected using setup data C64 to set Hour/min, Min/sec, 0.1
sec. Since a colon ": " cannot be displayed, the decimal point is used instead.)
(6) Press the ENTER key to stop the flashing on display panel 2.
(Pressing the FUNC and CLR keys causes display panel 1 and 2 to return to
unset state "-----" and the flashing stops.)
Output code setting
Set time value
Event number and sub number
Event type and No. of outputs
Unset values are indicated as "-----".
Timer code events use one subfunction. A subfunction cannot be used when a
setting has not been made "-----".
Events that follow the event number of a timer code event (number of output
points less 1) are skipped and not displayed.
– 1
PROG
Program
Segment
number
number
PROFILE
Pattern trend