WIRELESS INSTALLATION & INTEGRATION REFERENCE GUIDE FOR TB7200/TB7300/TB7600 SERIES THERMOSTATS
At the Job Site
1. Begin by positioning the controller with the wireless communication card centrally in the floor space you are working in.
2. Find the coverage radius of the controller at its proposed location. This coverage radius is the first hop from the controller.
Any thermostat or repeater should be NO FARTHER than 5 hops to and from the WEBs-AX controller with the wireless
communication card. This is due to the nature of the ZigBee stack in the wireless controllers. Walk about the floor where a
cluster of thermostats are to be installed. Locate the boundary where the signal strength is about 20%. The signal strength
can be viewed in the thermostat's property sheet in the Workbench in the TRSS field (Fig. 9).
Fig. 9. TRSS field shows signal strength.
7
63-4522—02