WIRELESS INSTALLATION & INTEGRATION REFERENCE GUIDE FOR TB7200/TB7300/TB7600 SERIES THERMOSTATS
network is another option. This will enable it to have a Zigbee address assigned by the wireless communication card of the
WEBs-AX controller or another thermostat. It will then enable the WEBs-AX controller to discover it; once discovered, re-install it
at the proper location.
3. Select the thermostats to add to the Station's database and click Add. The Add dialog box appears.
MORE INFORMATION ON ADDING DEVICES
At the bottom of the "WirelessTstatNetwork" folder, Add and Quick Add buttons are used to add devices to the network along with
other options.
New. The "New" thermostat button is a utility that allows the integrator to create offline devices prior to the installation. This allows
the integrator to pre-build a database and all related utilities before the actual installation takes place. When the assigned
thermostat would be automatically discovered in the field during commissioning, all required functions and bindings would
already be done and assigned.
Select the number of devices to add of the same type and the starting local MAC address each thermostat will be assigned in the
field.
Then select the required thermostat model number that will be installed on the job site. Remember to select ALL thermostats if
more than one is required. The thermostat can be enabled now or at a later date if the installation is done in segments. If the
devices in the field match the configuration of the devices created offline: PAN ID, Channel, Comm Address (MAC address) &
model number, they will automatically be matched to the devices created offline upon discovery.
Edit. Allows you to edit the characteristics assigned to any specific wireless thermostat. The thermostat name, Com Address and
enabled flag can be modified. The thermostat Model Type cannot be changed. If another model is required under the same
address, simply delete it and either create a new one offline or re-discover the proper one.
Match. When replacing thermostats or matching them in the field during the initial commissioning, this feature allows you to
match the characteristics of an offline created thermostat or an existing replaced one to a newly discovered one.