Object Name
RTC Communication Address
Config BO5 Outside Air Lockout Setpoint
Damper Minimum Position
Damper Maximum Position
Damper Max Heat Position
Heating Setpoint Limit
Cooling Setpoint Limit
Stand-By Time
Unoccupied Time
Dehumidification Hysteresis
Dehumidification Max Cooling
Economizer Changeover Setpoint
Economizer Minimum Position
Mixed Air Setpoint
High Balance Point
Low Balance Point
Dehumidification Low OA Lockout
Low RH Setpoint
Low Temp Reset RH Setpoint
High Temp Reset RH Setpoint
Damper Position
Heat Demand Limit
Cool Demand Limit
NOTE: Room Temperature, Outdoor Temperature and Room Humidity need to have their Boolean override counterpart object
set to "Override" first if the present value needs to be written over from the network. Ex To set a network present value
on the numeric "{Room Temperature" numeric object, the "Room Temperature Override" Boolean object needs to be set
from Normal to Override. The thermostat's local present value will then be derived from the wireless network instead of
the present value at the thermostat.
Object Type
Numeric Writable
none,min=1,max=127
Numeric Writable
temperature,min=-40,max=122
Numeric Writable
percent,min=0,max=100
Numeric Writable
percent,min=0,max=100
Numeric Writable
percent,min=0,max=100
Numeric Writable
temperature,min=40,max=90
Numeric Writable
temperature,min=54,max=100
Numeric Writable
hours,min=5.0,max=240.0
Numeric Writable
hours,min=5.0,max=240.0
Numeric Writable
percent,min=2,max=20
Numeric Writable
percent,min=20,max=100
Numeric Writable
temperature,min=14,max=70
Numeric Writable
percent,min=0,max=100
Numeric Writable
temperature,min=50,max=90
Numeric Writable
temperature,min=34,max=90
Numeric Writable
temperature,min=-40,max=30
Numeric Writable
temperature,min=-40,max=122
Numeric Writable
percent,min=10,max=90
Numeric Writable
temperature,min=-40,max=15
Numeric Writable
temperature,min=20,max=55
Numeric Writable
percent,min=0,max=100
Numeric Writable
percent,min=0,max=100
Numeric Writable
percent,min=0,max=100