W7212, W7213, W7214 ECONOMIZER LOGIC MODULES
Table 4. Checkout for W7212, W7213, W7214 Economizers Connected to Honeywell Actuator. (Continued)
Step
7.
HEAT PUMP INPUT - W7213, W7214 ONLY
Execute step one, Checkout Preparation.
Turn DCV MAX to mid position; set enthalpy potentiometer to A.
W7213: Jumper TR to B.
W7214: Remove jumper from TR and O.
63-2596—09
Checkout Procedure
—
Free cool LED turns on.
Actuator drives to 45 degrees open.
Free cool LED turns off.
Actuator drives fully closed.
22
Proper Response