Output Applications

The outputs on the Galaxy panels, with the exception of the SPCO relay output, are transistorised outputs;
negative applied (positive removed) by default. These supply up to 400 mA and can be used to drive the
necessary output devices.
NOTE:
The polarity of each output can be changed using option 53 = PROGRAM OUTPUTS
Transistorised Output
+12 V
Cut 3k3Ω to give
open collector
Figure 2-16. Output Configuration and Typical Applications
Note: For the appropriate 3k3Ω pull-up resistor refer to DIP switch SW3 (Table 2-1).
The relay output is a single pole change over; this can be used to drive output devices that require a clean set
of contacts, isolated from the output voltage.
Single Pole
Change - 0ver
relay contacts
Figure 2-17. Single Pole Change–Over Relay Output Configuration and Typical application
3k3Ω
Output
0 V
Normally
closed
Normally open
Output Applications
Typical Applications
A) LED
Output
LED
1kΩ (typical)
B) Bell
Bell
Output
C) Output used to trigger zone
Output
1%
1kΩ
1%
Output must be
1kΩ
open collector
Horn
2-17
+12 V
+ 12 V
zone
+12 V
0 V