Output Summary Table - This table shows all 12 functions (13 for –xFU2 models) for the
logic outputs terminals [11] and [12] at a glance. Detailed function descriptions, related param-
eters and settings, and example wiring diagrams are in
page
Option
Terminal
Code
Symbol
00
RUN
Run signal
01
FA1
Frequency arrival type
1 – constant speed
02
FA2
Frequency arrival type
2 – over-frequency
03
OL
Overload advance
notice signal
04
OD
Output deviation for
PID control
05
AL
Alarm signal
06
FA3
Frequency arrival type
3 – at frequency
08
IP
Instantaneous power
failure signal
09
UV
Under-voltage signal
11
RNT
Operation time over
12
ONT
Plug-in time over
4–35.
Output Function Summary Table
Function Name
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
"Using Intelligent Output Terminals" on
Description
Inverter is in Run Mode, motor running
Inverter is in Stop Mode, motor stopped
when output to motor is at the standard set frequency
F001
when output to motor is not at the set frequency F001
when output to motor is at or above the FA threshold
1(C042) during accel
when the output to motor is below the FA threshold 1
(C043) during decel
when output current is more than the set threshold for
the overload signal (set with C041)
when output current is less than the set threshold for
the overload signal
when PID error is more than the set threshold for the
deviation signal
when PID error is less than the set threshold for the
deviation signal
when the alarm condition has been met and not reset
when the alarm had not tripped since the previous
power cycle or since the previous keypad reset
when output to motor is at the FA threshold 1 (C042)
during accel, or at C043 during decel
when the output to motor is not at either the FA
threshold 1 (C042) during accel or at C43 during
decel
when the inverter input power has decreased below
the acceptable input voltage level
when the inverter input power is within rated range
when the inverter input power has decreased below
the acceptable input voltage level
when the inverter input power is within rated range
when the inverter Run time exceeds the limit set by
Run/power-on warning time (B034)
when the inverter Run time is less than the limit set by
Run/power-on warning time (B034)
when the inverter plug-in time exceeds the set limit
when the inverter plug-in time is less than the limit
3–49
L300P Inverter