CONFIGURING AN OUTUT FOR FAULT SIGNAL

The VFD will come from Detroit Hoist with output 16 (dry contact) already configured for fault alarm signal. If you need to switch the
fault alarm signal to a different output, use the chart below.
Function
Fault Alarm Signal

RESET FAULT USING INPUT

Resetting a fault remotely using an input to the VFD can be done by configuring one of the available digital inputs for reset. Use the
chart below.
Function
Fault reset

OUTPUT 0-10V / 4-20mA

The output analog can be configured for multiple functions. Listed below are the most common functions used for hoist and crane
applications. If the function is not present, please contact Detroit Hoist for further assistance.
Function
Ao1 – Analog output 1 function
Ao2 – Analog output 2 function
Analog monitor adjust mode
Ao1 filter time constant
Ao1 data type
Ao1 monitor bias adjustment
Ao1 monitor gain adjustment
Ao1 output level setting at Ao1
monitor adjust mode
Ao2 filter time constant
Ao2 data type
Ao2 monitor bias adjustment
Ao2 monitor gain adjustment
Ao2 output level setting at Ao2
monitor adjust mode
Parameters
CC-01 thru CC-05 (24vdc digital i/o)
CC-06 (16 relay dry contact)
Parameters
CA-04, CA-06
CA-08, CA-09
(when using encoder limits with parameters UE-33 = 2)
Parameters
dA-01 = Output Frequency
Cd-04
dA-02 = Output Current
Cd-05
dA-17 = Output Torque
0 = disabled
Cd-10
1 = enabled
Cd-21
1 – 500 ms
00 = Absolute data
Cd-22
01 = Signed data
Cd-23
-100.0 – 100.0%
Cd-24
-1000.0 – 1000.0%
Cd-25
-100.0 – 100.0%
Cd-31
1 – 500 ms
00 = Absolute data
Cd-32
01 = Signed data
Cd-33
-100.0 – 100.0%
Cd-34
-1000.0 – 1000.0%
Cd-35
-100.0 – 100.0%
Value
1 = Outputs to terminals output levels in the
Apply a gain to data to adjust an inclination in
Sets output in the adjustment mode. It selects
minimum output (at 0.0%) ([Cd-22]=00), or the
minimum output (at -100.0%) ([Cd-22]=01).
Apply a gain to data to adjust an inclination in
Sets output in the adjustment mode. It selects
minimum output (at 0.0%) ([Cd-32]=00), or the
minimum output (at -100.0%) ([Cd-32]=01).
Page 17
Value
017 = AL (Alarm)
Value
028 = RS
Description
adjustment mode.
Filters and outputs the selected data.
Outputs the absolute value of data
Outputs data with a symbol as is.
Biases data to adjust Point 0 of data.
data.
the maximum output (at 100.0%), the
Filters and outputs the selected data.
Outputs the absolute value of data
Outputs data with a symbol as is.
Biases data to adjust Point 0 of data.
data.
the maximum output (at 100.0%), the