Communications Reference Information

Inverter
The standard affirmative reply from the inverter
Affirmative Reply
uses the ACK character (acknowledge) in the data
field. The frame format of this reply follows the
diagram and specification table.
STX
Node
ACK
BCC
[CR]
Inverter
The standard negative reply from the inverter
uses the NAK character (negative acknowl-
Negative Reply
edge) in the data field. The frame format of
this reply follows the diagram and specifica-
tion table.
STX
Node
NAK
Error code
BCC
[CR]
The error codes for a NAK (negative acknowledge) are:
Element
Description
Control code (STart of TeXt)
Node (station) address of inverter
Control code (ACKnowledge)
Block check sum code
Control code (carriage return)
Element
Description
Control code (STart of TeXt)
Node (station) address of inverter
Control code
(Negative ACKnowledge)
Code representing error type
Block check sum code
Control code (carriage return)
Error
Error Description
Code
01H
Parity error
02H
Check sum error
03H
Framing error
04H
Overrun error
05H
Protocol error
06H
ASCII code error
L300P Inverter
Frame format
STX Node
ACK
Size
Value
1 byte
STX (0x02)
2 bytes 01 to 32
1 byte
ACK (0x06)
2 bytes Exclusive OR of Node and ACK
1 byte
[CR] (0x0D)
Frame format
Error
STX
Node
NAK
code
Size
Value
1 byte
STX (0x02)
2 bytes 01 to 32
1 byte
NAK (0x15)
2 bytes (See next table below)
2 bytes Exclusive OR of Node, Data,
and NAK
1 byte
[CR] (0x0D)
Error
Error Description
Code
07H
Receive buffer overrun error
08H
Receive time-out error
11H
Abnormal command code error
13H
Test error code
16H
Abnormal parameter code/value
error
B–17