Additional Analog Input Settings - Hitachi L300P Series Instruction Manual

Three-phase input 200v class; three-phase input 400v class;
Hide thumbs Also See for L300P Series:
Table of Contents

Advertisement

Additional
Analog Input
Settings
"A" Function
Func.
Name
Code
A101 [OI]–[L] input active
range start frequency
A102 [OI]–[L] input active
range end frequency
A103 [OI]–[L] input active
range start current
A104 [OI]–[L] input active
range end current
A105 [OI]–[L] input start
frequency enable
A111 [O2]–[L] input active
range start frequency
A112 [O2]–[L] input active
range end frequency
A113 [O2]–[L] input active
range start voltage
A114 [O2]–[L] input active
range end voltage
The parameters in the following table adjust the input characteristics of the analog inputs.
When using the inputs to command the inverter output frequency, these parameters adjust the
starting and ending ranges for the voltage or current, as well as the output frequency range.
Related characteristic diagrams are located in
Description
The output frequency corre-
sponding to the current input
range starting point.
Range is 0.00 to 400.0 Hz
The output frequency corre-
sponding to the current input
range ending point.
Range is 0.00 to 400.0 Hz
The starting point for the
current input range.
Range is 0 to 100%
The ending point for the
current input range.
Range is 0 to 100%
Two options:
00 Use A101 start value
01 Use 0Hz
The output frequency corre-
sponding to the bipolar
voltage input range starting
point.
Range is –400. to 400. Hz
The output frequency corre-
sponding to the bipolar
voltage input range ending
point.
Range is –400. to 400. Hz
The starting point for the
bipolar voltage input range.
Range is –100 to 100%
The ending point for the
bipolar voltage input range.
Range is –100 to 100%
"Analog Input Settings" on page
Defaults
Run
Mode
Edit
–FE2
–FU2
–FR
Lo Hi
(EU)
(US)
(JP)
✘ ✔
00.0
00.0
00.0
✘ ✔
00.0
60.0
00.0
✘ ✔
20.
20.
20.
✘ ✔
100.
100.
100.
✘ ✔
01
01
01
✘ ✔
0.00
0.00
0.00
✘ ✔
0.00
0.00
0.00
✘ ✔
-100. -100. -100.
✘ ✔
100.
100.
100.
3–27
L300P Inverter
3–11.
SRW Display
Units
Hz
>A101 INPUT-OI
EXS
0000.00Hz
Hz
>A102 INPUT-OI
EXE
0000.00Hz
%
>A103 INPUT-OI
EX%S
020%
%
>A104 INPUT-OI
EX%E
100%
Hz
>A105 INPUT-OI
LEVEL
0Hz
Hz
>A111 INPUT-O2
EXS
+000.00Hz
Hz
>A112 INPUT-O2
EXE
+000.00Hz
%
>A113 INPUT-O2
EX%S
-100%
%
>A114 INPUT-O2
EX%E
+100%