Smoke Verify (0900)
This setting controls the number of sensor group 26 (fire) zone
trips needed to report a fire alarm.
Hardwire Smokes: will determine whether or not the
panel requires two alarm signals within five minutes (on)
from 2-wire smoke detectors connected to panel zone input
6 and/or SnapCard zone inputs or any other hardwire zone
learned into group 26 (fire) before activating system sirens
and reporting to a central station (or pager).
Wireless Smokes: the first trip of a group 26 RF sensor
will cause a local fire alarm. The second trip of any group
26 zone within the siren timeout will cause that fire alarm
to be reported to the central station.
Note
RF smoke detectors repeat the alarm transmission every 60 sec-
onds as long as they are detecting smoke. This repeated transmis-
sion will serve as the second zone trip, causing the alarm to be
reported.
Two-Wire Smoke (0901)
This setting determines whether panel zone input 6 is set up for
2-wire smoke detectors (on) or for standard intrusion or 4-wire
smoke detectors (off).
Note
If 2-wire smoke detectors are connected to hardwire zone input 6,
this setting must be turned on before entering the LEARN SEN-
SORS menu.
Output 1, 2 (09100-output 1) (09110-output 2)
This setting lets you assign the selected output a 5-digit config-
uration number that determines which system event activates
the output and the duration or time the output is activated.
The first three digits represent the trigger number of an event,
such as an alarm, open sensor, or arming the system.
The last two digits represent how the output responds, such as
momentary, sustained (or latched), or for a preset time.
Tables A6-A10 in "Appendix A" identify system event trigger
and response numbers.
Programming the Panel
—this menu lets you assign the two built-in panel outputs to partitions and set their con-
OUTPUTS
figuration numbers.
The following describes how to program the settings that appear under
.
INPUTS

Exiting Programming Mode

After all installer/dealer programming is completed, use the following procedure to exit program-
ming mode.
¾
To exit programming mode:
1. Press ‚ until the display shows
2. Press A once and the display shows
Onboard Options-Inputs (Default=off)
¾
To turn Smoke Verify off or on:
1. With the display showing
twice. The display shows
setting).
2. Press 1 (off) or 2 (on). The display flashes the entered num-
ƒ and the display shows the new setting.
ber. Press
Note
For California State Fire Marshall Listed installations, this feature
must be off.
Onboard Options-Inputs (Default=off)
¾
To turn Two-Wire Smoke off or on:
1. With the display showing
twice, then B once. The display shows
(current setting).
OFF/ON
2. Press 1 (off) or 2 (on). The display flashes the entered
number. Press ƒ and the display shows the new setting.
Onboard Options-Inputs (Defaults: Output 1=00410,
¾
To set up onboard Output 1 & 2 partition and configura-
tion assignments:
1. With the display showing
B . The display shows
OUTPUT PROGRAMMING
2. Press ƒ and the display shows
.
OUTPUT 2
3. After selecting the desired output, press ƒ . The display
shows
CONFIGURATION
4. Enter the desired configuration number. The display
flashes the entered number. Press ƒ and the display shows
the new setting.
.
SYSTEM PROGRAMMING
EXIT PROGRAMMING
ONBOARD OPTIONS—
, press ƒ
ONBOARD OPTIONS
(current
SMOKE VERIFY OFF/ON
, press ƒ
ONBOARD OPTIONS
TWO WIRE SMOKE
Output 2=01710)
, press ƒ +
ONBOARD OPTIONS
.
. Press B to select
OUTPUT 1
(current setting).
.