Install an end-of-line resis-
tor on all unused, factory
programmed, onboard panel
zones.
9
8642137A.DSF
Figure 7. Installing and Connecting the HIM in the Concord Express

Connecting Detection Devices to Panel Zone Inputs

The panel comes with six factory programmed onboard hardwire zones (see "Accessory Modules
Menu" on page 40 for factory settings). Zone inputs 1 through 6 are supervised using a 2k-ohm,
end-of-line resistor (included with panel) at the last device on the circuit.
All six zones accept either normally open (N/O) or normally closed (N/C) detection devices (see
Figure 8).
The maximum loop resistance for each zone input is 300 ohms, plus the 2k end-of-line (EOL)
resistor.
Connecting Intrusion Detection Devices
Figure 8 shows the typical wiring for N/C and N/O door/window intrusion detection.
Panel Terminals
Normally
Closed
(N/C)
Contacts
in Series
2k Ohm
EOL Resistor
(49-454)
Figure 8. Connecting N/C and N/O Intrusion Detection Circuits
Figure 9 shows the typical wiring for Optex model RX-040 (PI) PIR motion detectors. The mini-
mum available panel voltage for hardwired PIR motion detectors is 8.5 VDC (9.1 VDC for UL
Listed systems).
To Zone Input Device
Normally
Open
(N/O)
Contacts
in Parallel
2k Ohm
EOL Resistor
(49-454)
(Shared Commons)
Panel Terminals