Note
Install all sirens/speakers
indoors, in a concealed loca-
tion.
Note
If the backup battery is not
connected, or if the configu-
ration of panel terminal 7 is
programmed to anything
other than the default
(00410), then the combined
currents of terminal 7 (OUT
1/+12) and terminal 4 (+12V)
must not exceed 750 mA.
Note
For UL Listed systems,
Siren Verify must be on.
Installing the System
2k Ohm
EOL Resistor
(49-454)
Locate at
Last Device
2k Ohm
EOL Resistor
(49-454)
Locate at
Last Device
Figure 11. Connecting 4-Wire Smoke Detectors

Connecting Sirens

Two onboard programmable outputs allow for siren connections when using the default setting
of each output. For more information on output configuration numbers, see the section "Pro-
gramming the Panel" and the tables in Appendix A.
The following describes siren connections using the default settings of each onboard output.
15-Watt, Dual Tone Siren (13-469)
Panel terminal 7 (OUT1/+12V) is a +12V programmable output. At the default configuration
setting (00410), this output can provide up to 1.25 A during an alarm (650 mA for UL Listed
systems) if the backup battery is connected.
The default configuration setting (00410) activates the output during any audible alarm, allow-
ing for a siren connection without changing the output configuration number.
Black (Common)
Yellow (Steady)
Concord
Express
Panel
Red
Terminals
(Not Used)
Figure 12. Connecting 15-Watt, Dual-Tone Siren 13-469
Panel Terminal 8 (OUT2/OC)
Must be Set to Configuration
Number 01500 for Connected
Smoke Detectors to Reset
After Canceling a Fire Alarm
Model
449AT
Model
449AT
12