When you receive your D400, it is configured with default communication settings. To
enable the D400 to communicate over your network, you must change the settings as
required by your system.
6.1
Connecting to the D400 for the First Time
To perform the initial set up of the D400, you need to plug directly into the D400 through
the front serial communications port. The front communications port provides a local
connection and terminal session with the D400 used to perform system administrative
and maintenance procedures.
»
To connect to the D400:
Connect the supplied null modem cable (GE Part No. 977-0529/72) to your
1.
computer's serial communications port and to the D400's front communications port.
See section "4.10 Front Maintenance Port" for cabling information.
From the Windows Start menu, select Programs > Accessories > Communications >
2.
HyperTerminal.
The HyperTerminal window opens and a connection wizard starts.
In the Connection Description dialog box, enter a Name for the connection. Click OK.
3.
Note: The name you choose is not important.
In the Connect to dialog box, select your computer's communication port (typically
4.
COM1) in the Connect using list. Click OK.