GE D400 Substation Data Manager User Manual page 18

Table of Contents

Advertisement

GE Energy
Environmental
Operating temperature
Humidity rating
Environmental rating
Installation / overvoltage
category
Pollution degree
Use
Altitude
Software
Firmware
Human machine interface
Configuration
Soft logic
1.5
Storage Recommendations
Storage Conditions
Always store the D400 in an environment compatible with operating conditions.
Recommended environmental conditions for storage are:
Temperature: -40 °C to +90 °C
Relative humidity: 5 % to 95 %, non-condensing
Exposure to excessive temperature or other extreme environmental conditions might
cause damage and/or unreliable operation.
Battery Life
To maintain the life of the battery, you should remove the battery if the D400 will be
powered down or stored for more than six months.
See section "7.2 Replacing the Battery".
18
994-0089–1.00–2, General
-20 °C to +65 °C
Maximum ambient temperature is +50 °C for unit to fully
comply with IEC 61010-1 Section 10.1 regarding surface
temperature limits for protection against burns.
5 % to 95 % relative humidity, non-condensing
Ingress protection: IP30 (IEC 60529)
CAT III
2
Indoor use only
Maximum altitude 10,000 ft [3000 m]
Embedded application dependent
Built-in graphical user interface (Web browser-based)
Built-in graphical user interface (Web browser-based)
Offline Configuration Manager (PC-based) - Future
IEC 61131-3 soft logic engine - Future
LogicLinx* Editor (if using LogicLinx)
Get other manuals https://www.bkmanuals.com