Program
Soft Keys
ZONE LABEL: Press to type in a 20-character maximum zone description that will appear in the
zone's display messages.
ACCEPT: Press to save the message and return to the previous screen.
3.4.4 Releasing Zone
Releasing Zone Programming
This screen displays when a releasing zone is chosen at the Point Program menu (see Figure 3.24
on page 39).
Refer to Appendix B, "Releasing Applications" for a full explanation of the fields below.
Soft Keys
DELAY TIME: Press this soft key to type a value from 0 to 60 (seconds). Default 00
ABORT SWITCH: Press this soft key to scroll through the selection list of ULI, IRI, NYC, or AHJ.
Default:ULI
50
Z O N E P O I N T P R O G R A M M I N G
Z O N E L A B E L :
Figure 3.35 Zone Point Programming Screen
R E L E A S I N G Z O N E P R O G R A M M I N G M E N U
D E L A Y T I M E : 0 0
A B O R T S W I T C H : U L I
C R O S S Z O N E : N O
S O A K T I M E : 0 0 0 0
Figure 3.36 Releasing Zone Programming Menu Screen
NFS2-3030 Programming Manual — P/N 52545:A 11/29/2005
Z y y y
Z R 0 8
Point Program
A C C E P T
B A C K
A C C E P T