Extended Function Mode - Hitachi SJ700-055-110LF 2 Series Service Manual

Table of Contents

Advertisement

1.2.3 Extended Function Mode

Code
Function name
Frequency source setting
A001
Run command source setting
A002
A003
Base frequency setting
Base frequency setting, 2nd
A203
motor
Base frequency setting, 3rd
A303
motor
A004
Maximum frequency setting
Maximum frequency setting, 2nd
A204
motor
Maximum frequency setting, 3rd
A304
motor
[AT] selection
A005
[O2] selection
A006
[O]-[L] input active range start
A011
frequency
[O]-[L] input active range end
A012
frequency
[O]-[L] input active range start
A013
voltage
[O]-[L] input active range end
A014
voltage
[O]-[L] input active range start
A015
frequency selection
External frequency filter time
A016
const.
Easy sequence function
A017
selection
Multispeed operation selection
A019
A020
Multispeed frequency setting
Multispeed frequency setting,
A220
2nd motor
Multispeed frequency setting,
A320
3rd motor
A021
Multispeed 1 setting
A022
Multispeed 2 setting
A023
Multispeed 3 setting
A024
Multispeed 4 setting
A025
Multispeed 5 setting
A026
Multispeed 6 setting
A027
Multispeed 7 setting
A028
Multispeed 8 setting
A029
Multispeed 9 setting
A030
Multispeed 10 setting
A031
Multispeed 11 setting
A032
Multispeed 12 setting
A033
Multispeed 13 setting
A034
Multispeed 14 setting
A035
Multispeed 15 setting
A038
Jog frequency setting
A039
Jog stop mode
.
All manuals and user guides at all-guides.com
Monitored data or setting
00 (keypad potentiometer) (*1), 01 (control circuit terminal block), 02 (digital
operator), 03 (RS485), 04 (option 1), 05 (option 2), 06 (pulse-string input), 07
(easy sequence), 10 (operation function result)
01 (control circuit terminal block), 02 (digital operator), 03 (RS485), 04 (option
1), 05 (option 2)
30. to "maximum frequency " (Hz)
30. to "maximum frequency, 2nd motor" (Hz)
30. to "maximum frequency, 3rd motor" (Hz)
30. to 400. (Hz)
30. to 400. (Hz)
30. to 400. (Hz)
00 (switching between O and OI terminals), 01 (switching between O and O2
terminals), 02 (switching between O terminal and keypad potentiometer) (*1),
03 (switching between OI terminal and keypad potentiometer) (*1), 04
(switching between O2 and keypad potentiometer) (*1)
00 (single), 01 (auxiliary frequency input via O and OI terminals)
(nonreversible), 02 (auxiliary frequency input via O and OI terminals)
(reversible), 03 (disabling O2 terminal)
0.00 to 99.99, 100.0 to 400.0 (Hz)
0.00 to 99.99, 100.0 to 400.0 (Hz)
0. to "[O]-[L] input active range end voltage" (%)
"[O]-[L] input active range start voltage" to 100. (%)
00 (external start frequency), 01 (0 Hz)
1. to 30. or 31. (500 ms filter ±0.1 Hz with hysteresis)
00 (disabling), 01 (enabling)
00 (binary: 16 speeds selectable with 4 terminals), 01 (bit: 8 speeds selectable
with 7 terminals)
0.0 or "start frequency" to "maximum frequency" (Hz)
0.0 or "start frequency" to "maximum frequency, 2nd motor" (Hz)
0.0 or "start frequency" to "maximum frequency, 3rd motor" (Hz)
0.0 or "start frequency" to "1st maximum frequency" (Hz)
0.0 or "start frequency" to "2nd maximum frequency" (Hz)
0.0 or "start frequency" to "3rd maximum frequency" (Hz)
0.0 or "start frequency" to "n-th maximum frequency" (Hz)
0.0 or "start frequency" to "n-th maximum frequency" (Hz)
0.0 or "start frequency" to "n-th maximum frequency" (Hz)
0.0 or "start frequency" to "n-th maximum frequency" (Hz)
0.0 or "start frequency" to "n-th maximum frequency" (Hz)
0.0 or "start frequency" to "n-th maximum frequency" (Hz)
0.0 or "start frequency" to "n-th maximum frequency" (Hz)
0.0 or "start frequency" to "n-th maximum frequency" (Hz)
0.0 or "start frequency" to "n-th maximum frequency" (Hz)
0.0 or "start frequency" to "n-th maximum frequency" (Hz)
0.0 or "start frequency" to "n-th maximum frequency" (Hz)
0.0 or "start frequency" to "n-th maximum frequency" (Hz)
"Start frequency" to 9.99 (Hz)
00 (free-running after jogging stops [disabled during operation]), 01
(deceleration and stop after jogging stops [disabled during operation]), 02 (DC
braking after jogging stops [disabled during operation]), 03 (free-running after
jogging stops [enabled during operation]), 04 (deceleration and stop after
jogging stops [enabled during operation]), 05 (DC braking after jogging stops
[enabled during operation])
1 - 4
Default
Note
_FF
_FEF
_FUF
02
01
01
02
01
01
60.
50.
60.
60.
50.
60.
60.
50.
60.
60.
50.
60.
60.
50.
60.
60.
50.
60.
00
03
0.00
0.00
0.
100.
01
31.
00
00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
1.00
00