Initialization Setting - Hitachi SJ700-055-110LF 2 Series Service Manual

Table of Contents

Advertisement

2.5 Initialization setting

The initialization function allows you to initialize the adjusted settings on the inverter to restore the factory settings. You
can also clear the trip history data alone.
The settings of initialization are described below.
The settings of "P100" to "P131", running-time data, and power-on time data cannot be cleared.
Item
Initialization mode
(parameters or trip
history)
Country code for
initialization
(Initializing procedure)
Adjust the above settings as required, and then perform the following procedure:
1) Holding down the FUNC and [2]
(down) keys, press and hold down
the STOP/RESET key.
- After the monitor starts blinking,
release only the STOP/RESET
key. (The display on the monitor
changes to that shown in the
middle figure above.
- Release the FUNC and [2]
(down) keys.
Initialization-in-progress
display intended for Europe
Initialization-in-progress
display intended for the U.S.A.
Initialization-in-progress display for
trip history clearance
Note 1: The initialization operation does not initialize the analog input settings (C081, C082, C083, C121,
C122, and C123) and thermistor coefficient setting (C085).
Note 2: The initialization operation does not initialize the settings of easy sequence user parameters
(P100 to P131).
All manuals and user guides at all-guides.com
Function code
Data
b084
b085
2) Initialization is in progress.
- The above figure shows the
monitor display (indicating that the
initialization is in progress)
intended for Japan. Those
intended for other regions and trip
history clearance are shown
below.
In the far-left digit, the lighting
segments move round for
2 - 11
00
Clearing on the trip history data
Initializing only the settings
01
The factory settings are restored.
Clearing the trip history data and initializing the
02
settings
00
Defaults intended for Japan
01
Defaults intended for Europe
02
Defaults intended for the U.S.A.
3) When the initialization is
Description
completed, the monitor displays
code "d001".
Confirm that the settings have
been initialized.

Advertisement

Table of Contents
loading