Code
Function name
d025
User monitor 0
d026
User monitor 1
d027
User monitor 2
d028
Pulse counter
d029
Position setting monitor
d030
Position feedback monitor
d080
Trip Counter
Trip monitoring 1
d081
Trip monitoring 2
d082
Trip monitoring 3
d083
Trip monitoring 4
d084
Trip monitoring 5
d085
Trip monitoring 6
d086
d090
Programming error monitoring
d102
DC voltage monitoring
d103
BRD load factor monitoring
d104
Electronic thermal overload monitoring

1.2.2 Function Mode

Code
Function name
Output frequency setting
F001
F002
Acceleration (1) time setting
F202
Acceleration (1) time setting, 2nd
motor
F302
Acceleration (1) time setting, 3rd
motor
F003
Deceleration (1) time setting
F203
Deceleration time setting, 2nd motor
F303
Deceleration time setting, 3rd motor
F004
Keypad Run key routing
All manuals and user guides at all-guides.com
Monitored data or setting
-2147483647 to 2147483647 (upper 4 digits including "-")
-2147483647 to 2147483647 (upper 4 digits including "-")
-2147483647 to 2147483647 (upper 4 digits including "-")
0 to 2147483647 (upper 4 digits)
-1073741823 to 1073741823 (upper 4 digits including "-")
-1073741823 to 1073741823 (upper 4 digits including "-")
0. to 9999., 1000 to 6553 (10000 to 65530) (times)
Factor, frequency (Hz), current (A), voltage across P-N (V), running time (hours),
power-on time (hours)
Factor, frequency (Hz), current (A), voltage across P-N (V), running time (hours),
power-on time (hours)
Factor, frequency (Hz), current (A), voltage across P-N (V), running time (hours),
power-on time (hours)
Factor, frequency (Hz), current (A), voltage across P-N (V), running time (hours),
power-on time (hours)
Factor, frequency (Hz), current (A), voltage across P-N (V), running time (hours),
power-on time (hours)
Factor, frequency (Hz), current (A), voltage across P-N (V), running time (hours),
power-on time (hours)
Warning code
0.0 to 999.9 (V)
0.0 to 100.0 (%)
0.0 to 100.0 (%)
Monitored data or setting
0.0, "start frequency" to "maximum frequency" (or maximum frequency,
2nd/3rd motors) (Hz)
0.0 to 100.0 (when PID function is enabled)
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)
00 (forward rotation), 01 (reverse rotation)
1 - 3
Note
Default
Default
_FF
_FEF
_FUF
0.00
30.00
30.00
30.00
30.00
30.00
30.00
00