3.2 Function Modes

No.
Function name
5
Function for factory adjustment
6
Region code for inverter
7
Capacity code for inverter
8
Voltage class code for inverter
9
Inverter mode

3.3 How To Reference the Data Area (d105) Corresponding to Trip History

In the data area you can directly reference the factors (determined by the gate array) of the past six trips. Do not
change the value set as "C172".
(1) Specify "FFFF" for "C170".
(2) Specify "A56A" for "C171".
(3) Reference the data of "C172". Record the last two digits of the data. (The range of data is "**00" to "**05".)
(4) Specify one of the values listed in the table below for "C171" according to the target trip history data and the value
of "C172".
Target
history
**00
data
d081
A56E
d082
A5D2
d083
A5BE
d084
A5AA
d085
A596
d086
A582
Example 1: Referencing the history data of "d083" when "C172" is "**02"
(1) As shown in the above table, the data of "d083" is "A56E" when "C172" is "**02".
(2) Specify "A56E" for "C171".
(5) Reference the value displayed as "C172". The first two digits of the 4-digit value displayed correspond to the value
of "d105".
□□□□
Code of the trip factor determined by gate array
Example 2:
When the value of "C172" is "08**", the trip factor is overvoltage protection because bit 3 is "1".
 
 
 
 
 
 
 
 
 
 
 
 
 
 
All manuals and user guides at all-guides.com
Function code
C170-C194
C195
C196
C197
C198
Value of "C172"
**01
**02
A582
A596
A56E
A582
A5D2
A56E
A5BE
A5D2
A5AA
A5BE
A596
A5AA
Range of data
Change inhibited
JP (intended for Japan)
0.2 to 55.0 (kW)
200 (200 V class) or 400 (400 V class)
00(SJ700)
**03
**04
A5AA
A5BE
A596
A5AA
A582
A596
A56E
A582
A5D2
A56E
A5BE
A5D2
**05
A5D2
A5BE
A5AA
A596
A582
A56E