Precautions For Data Setting - Hitachi SJ700-055-110LF 2 Series Service Manual

Table of Contents

Advertisement

1.2 Precautions for Data Setting

The default display mode limits the screens (parameters) that can be displayed on the monitor. To enable the display
of all parameters, specify "00" (full display) for the function code display restriction (b037).
To enable the parameters to be changed while the inverter is operating, specify "10" for the software lock mode
selection (b031).
1.2.1 Monitoring Mode
Code
Function name
d001
Output frequency monitoring
d002
Output current monitoring
d003
Rotation direction minitoring
d004
Process variable (PV), PID feedback
monitoring
d005
Intelligent input terminal status
d006
Intelligent output terminal status
d007
Scaled output frequency monitoring
d008
Actual-frequency monitoring
d009
Torque command monitoring
d010
Torque bias monitoring
d012
Torque monitoring
d013
Output voltage monitoring
d014
Power monitoring
d015
Cumulative power monitoring
d016
Cumulative operation RUN time
monitoring
d017
Cumulative power-on time monitoring
d018
Heat sink temperature monitoring
d019
Motor temperature monitoring
d022
Life-check monitoring
d023
Program counter
d024
Program number monitoring
All manuals and user guides at all-guides.com
Monitored data or setting
0.00 to 99.99, 100.0 to 400.0 (Hz)
0.0 to 999.9, 1000 to 9999 (A)
F (forward rotation), o (stopped), r (reverse rotation)
0.00 to 99.99, 100.0 to 999.9, 1000. to 9999.
1000 to 9999 (10000 to 99990), 100 to 999 (100000 to 999000)
(Example)
FW
Terminals FW, 7, 2, and 1: ON
Terminals 8, 6, 5, 4, and 3: OFF
6
4
8
7
5
3 2
1
(Example)
Terminals 12 and 11: ON
Terminals AL, 15, 14, and 13: OFF
AL 15 14 13 12
11
0.00 to 99.99, 100.0 to 999.9, 1000. to 9999., 1000 to 3996 (10000 to 39960)
-400. to -100., -99.9 to 0.00 to 99.99, 100.0 to 400.0 (Hz)
-200. to +200. (%)
-200. to +200. (%)
-200. to +200. (%)
0.0 to 600.0 (V)
0.0 to 999.9 (kW)
0.0 to 999.9, 1000. to 9999.
1000 to 9999 (10000 to 99990), 100 to 999 (100000 to 999000)
0. to 9999., 1000 to 9999 (10000 to 99990), 100 to 999 (100000 to 999000) (hr)
0. to 9999., 1000 to 9999 (10000 to 99990), 100 to 999 (100000 to 999000) (hr)
-020. to 200.0 ( C)
-020. to 200.0 ( C)
1: Capacitor on main circuit board
2: Cooling-fan speed drop
ON
OFF
2
1
0 to 1024
0000 to 9999
1 - 2
Note
Default

Advertisement