Chapter 3
Chapter 3
Operation Setting and
Examples of I/O Adjustment
This chapter describes basic settings,
example of frequency reference destination selection
and setting , example of RUN command destination
selection and setting and example of analog
input/output adjustment.
◼ Basic settings 1

3.1 Set the load rating

Select [Ub-03] load specification selection on the
parameter setting screen.
−
When [Ub-03] is changed, the parameters set for the
current are automatically adjusted in proportion to the
changed rated current, and the set values are changed.
Therefore, change the parameters value for setting the
current value such as electronic thermal , overload
limit, etc., so change [Ub-03] first.
◼ Parameter
Parameter
Details
Load type
[Ub-03]
selection.
*) The underlined value is set by default.
Note:
The rated load types of
SH1-03410-H(SH1-1600H)~SH1-04810-H(SH1-2200H) are
available for normal duty(ND) and low duty(LD).
Operation Setting and Examples of I/O Adjustment
Setting data
00: Very Low Duty (VLD)
01: Low Duty (LD)
02: Normal Duty (ND)
3-1
See "Chapter 4 Settings" for detailed operating
instructions
◼ Basic settings 2

3.2 Set the motor data

Set the parameters listed in the table below on the
parameter setting screen according to the motor you
use (e.g. induction motor and permanent-magnet
motor).

◼ Parameter
Induction motor (IM)
Parameter
Details
Control mode selection,
[AA121]
1st-motor
[Hb102]
Async. Motor capacity
setting, 1st-motor
Async. Motor number of
[Hb103]
poles setting, 1st-motor
Async.
Motor
[Hb104]
frequency
setting ,1st-motor
Async. Motor maximum
[Hb105]
frequency
setting ,1st-motor
Async.
Motor
[Hb106]
voltage,1st-motor
Async.
Motor
[Hb108]
current, 1st-motor
Synchronous motor (permanent-magnet motor) SM(PMM))
Parameter
Details
Control mode selection,
[AA121]
1st-motor
[Hd102]
Sync. Motor
setting,1st-motor
Sync. Motor number of
[Hd103]
poles setting, 1st-motor
Sync. Base frequency
[Hd104]
setting,1st-motor
Sync. Maximum
[Hd105]
frequency
setting, 1st-motor
Sync.
Motor
[Hd106]
voltage,1st-motor
Sync.
Motor
[Hd108]
current, 1st-motor
Note: Motor constant setting is required for driving SM.
Setting data
00: [V/f] Fixed torque
characteristics (IM) , etc.
0.01 to 160.00 (kW)
(In the case of
SH1-1600H or more
0.01 to 500.00(kW) )
2 to 48 (poles)
base
10.00 to 590.00 (Hz)
10.00 to 590.00 (Hz)
rated
1 to 1000 (V)
rated
0.01 to 10000.00 (A)
Setting data
11: Synchronous start type
sensorless vector
control(SM/PMM)) , etc
0.01 to 160.00 (kW)
capacity
(In the case of
SH1-1600H or more
0.01 to 500.00(kW) )
2 to 48 (poles)
10.00 to 590.00 (Hz)
10.00 to 590.00 (Hz)
rated
1 to 1000 (V)
rated
0.01 to 10000.00 (A)