1MRK506371-UUS Rev. M
The supported list of hints are as follows:
Table 51:
Headline
Incorrect setting of SyncLostMode
Sampled value substituted
Time diff: IED vs Sampled value
Frequency diff: IED vs Sampled value
Wrong cycle time for PMU report
PMU not connected to 3ph output
Invalid value set for PMU Parameters
Invalid phase angle reference
GOOSE is configured on a disabled port
Table continues on next page
Line distance protection REL670
Commissioning manual
The Hint menu is currently only available in English. All the entries are in English, regardless
of which language is selected.
Hint menu
© 2017 - 2023 Hitachi Energy. All rights reserved
Explanation
There are two explanations possible:
SyncLostMode is set to Block, no time source is configured
to achieve the required accuracy. Unless a high accuracy
time source is selected, the function dependent on high time
accuracy will be blocked.
SyncLostMode is set to BlockOnLostUTC, but there is no
UTC capable synch source (GPS, IRIG-B) used. Unless a
UTC capable time source is selected, the function
dependent on high time accuracy will be blocked.
<Access Point><Hardware Module Identifier><svID>
Where the Hardware Module Identifier is the same as given
in PCM600, e.g. AP1: MU1_9201 svID: <Hitachi Energy
_MU0101>
<Access Point><Hardware Module Identifier><svID>
Where the Hardware Module Identifier is the same as given
in PCM600, e.g. AP1: MU1_9201 svID: <Hitachi Energy
_MU0101>
<Access Point><Hardware Module Identifier><svID>
Where the Hardware Module Identifier is the same as given
in PCM600, e.g. AP1: MU1_9201 svID: <Hitachi Energy
_MU0101>
Wrong cycle time on SMAI or 3PHSUM block connected to
Phasor Report block. The SMAI or 3PHSUM block should
have same cycle time as that of Phasor Report.
The PMU phasor report input(s) must be connected to the
3ph output of SMAI or 3PHSUM.
There are two possible error conditions:
Check if the following parameters are set correctly on
PMUREPORT:1 ReportRate or SvcClass or parameter
PRIMVAL:1.FrequencySel is not set as 50Hz / 60Hz.
Check if the following parameters are set correctly on
PMUREPORT:1 ReportRate or SvcClass or RptTimetag or
parameter PRIMVAL:1.FrequencySel is not set as 50Hz /
60Hz.
The selected PhaseAngleRef corresponds to an analog
channel that is not configured. Configure a valid reference
channel.
At least one of the access points configured for GOOSE is
disabled. The port can be disabled either through changing
the access point operation to off or by unchecking the
GOOSE protocol from the access point in the Ethernet
configuration in PCM600 or LHMI.
Enable GOOSE on access points:
<Access Points>, can be any of these: AP_FRONT, AP_1,
AP_2, AP_3, AP_4, AP_5, AP_6,AP_7, AP_8
Section 14
Troubleshooting
263