Hitachi Relion 670 Series Commissioning Manual page 207

Line distance protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK506371-UUS Rev. M
2.
Set the constant voltage input of UL1 = 63.5V at 0° and UL2 = 63.5V at 120° and UL3 at 63.5 -120°
secondary at rated frequency.
3.
Based on the mode of operation, carry out the following changes on input condition of Step
detect pickup condition.
Each mode is given for increase and decrease operation. (3-a and 3-b)
Step No.
3-a
3-b
3-a
3-b
3-a
3-b
4.
Repeat Step
11.9.4.2
Completing the test
Continue to test another function or end the test by changing the TestMode setting to Disabled. Restore
connections and settings to their original values, if they were changed for testing purposes.
11.9.5
Current based delta supervision DELISPVC(7I)
Prepare the IED for verification of settings outlined in Section
11.9.5.1
Verifying the signals and settings
Make sure that the function is connected to SMAI function with I3P signal.
Delta supervision function has four different modes of operation. Proceed as follows to test the function in
a particular mode.
1.
Set the following parameters:
Line distance protection REL670
Commissioning manual
DelUang> = 10°
DeltaT = 2
tHold = 100
OpMode
Instantaneous 1 cycle
or Instantaneous 2
cycle
Instantaneous 1 cycle
or Instantaneous 2
cycle
RMS or DFT Mag
RMS or DFT Mag
DFT Angle (vector
shift)
DFT Angle (Vector
shift)
3
with UL2 changes for different mode.
Operation = ON
MeasMode = Phase-to-ground
Imin = 10% of IBase
© 2017 - 2023 Hitachi Energy. All rights reserved
Changes after step 2
Change UL1 to 20V
Change UL1 back to 63.5V
Change UL1 to 20V
Change UL1 back to 63.5V
Change UL1 to 63.5V at 15°
without changing frequency
Change UL1 to 63.5V at 0°
without changing frequency
"Preparing the IED to verify
Testing functionality by secondary injection
Expected output
STL1 , STLOW, BFI_3P signal should be TRUE
for 100 ms
STL1 , STRISE, BFI_3P signal should be
TRUE for 100 ms
STL1, STLOW, BFI_3P signal should be TRUE
for 100 ms
STL1 , STRISE, BFI_3P signal should be
TRUE for 100 ms
STL1, BFI_3P signal will be TRUE for 100 ms.
STL1, BFI_3P signal will be TRUE for 100 ms
GUID-2FE5E5F0-0E6C-499E-93D2-471C183B89BF v2
GUID-9EAEFF02-62C2-4FA7-8F3D-E92391206F7F v2
settings".
GUID-86324E4D-E054-495F-9D64-29741FBD8CBE v2
Section 11
2
to
201