General Specification - Honeywell Sensepoint XCD RFD Technical Manual

Remote flammable detector
Hide thumbs Also See for Sensepoint XCD RFD:
Table of Contents

Advertisement

Sensepoint XCD RFD Technical Manual

14 General specification

Sensepoint XCD Transmitter
Use
3-wire, 4-20mA, gas detector transmitter for use with remotely mounted flammable gas detectors.
Electrical
Input Voltage Range:
Max Power Consumption:
Current output
≥0.0<1.0 mA
4.0 mA to 20.0 mA
2.0 mA or 4.0 mA
22.0 mA
Terminals
Relays
Communication
Construction
Material
Epoxy painted aluminum alloy or 316 Stainless Steel
Weight
Aluminum alloy: 1.7kg, 316 Stainless Steel: 3.7kg
Mounting
Pole or wall mounting
Cable Entries
2 x 3/4"NPT (for cCSAus/UL Approval)
Sensor Entries
3/4"NPT (for cCSAus/UL Approval)
Detectable Gases & Performance (See notes below)
Gas
Selectable Full
Default
Scale Range
Range
705 Standard Temperature Sensor
Flammable 1 to 8* 20 to 100%LEL
100%LEL
705 High Temperature Sensor
Flammable 1 to 8*
20%LEL
20%LEL
Flammable 1 to 8* 20 to 100%LEL
100%LEL
*Contact Honeywell Analytics for availability
705
Hydrogen
*6
Methane
*6
Butane
*3
Propane
*3
Pentane
*2
Ethylene
*4
NOTES
Performance figures are taken at 20~25℃;
1. measured using a sample humidity of 50%RH, applicable between 10 and 90% of full scale,
2. measured using test units calibrated at 50% of full scale,
3. measured at 1000cc/min for Methane CAT, 500cc/min for Methane IR with calibration cup (S3KCAL).
Response time (T90) may increase when operating in lower or higher temperature conditions or when gas is introduced with the Weather
Protection accessory (SPXCDWP) fitted. Should it be exposed to other HC then non linear response is expected. For linearised operation
other than Methane contact HA for alternate parts. This calibration enables 100% functional test prior to dispatch.
This calibration does not remove need for calibration & test as part of commissioning at site. For gases other than Methane the unit has
to be calibrated at site using target gas.Data represents typical values, and system conditioning may be required to achieve stated result.
Contact HA for details.
* Extended operating temperature range of -40°C to +65°C (-40°F to +149°F) for all sensor , with an accuracy of +/- 30% of applied gas
from -20°C to -40°C (-4°F to -40°F) and +55°C to +65°C (+131°F to +149°F). Long term operation at this range may cause decline in
sensor performance.
Contact Honeywell Analytics for any additional data or details.
Certification
International
IEC Ex II 2 GD Ex d IIC Gb T6(Ta -40ºC to +65ºC) Ex tb IIIC T85ºC Db IP66
North America
cCSAus Class I, Division 1, Groups B, C & D
Latin America
Inmetro, Ex d IIC T6 Gb; Ex tb IIIC T85°C Db IP66, -40°C < Ta < +65°C;
Ex d IIC T5 Gb, Ex tb IIIC T 100°C Db, IP66 -40°C < Ta < +75°C
Performance
C22.2-152, ISA 121301
Note: Performance approval is based on the standard 705 sensor calibrated to Methane
EN50270:2006 EN6100-6-4:2007
CE
Environmental
IP Rating
IP66 in accordance with EN60529:1992, NEMA 4X (Tested by third party laboratory)
Operating
-40ºC to +65ºC/ -40ºF to +149ºF, (IR: -20ºC to +50ºC/ -4ºF to +122ºF).
Temperature
Note: The detector display may become illegible at temperatures below -20°C, but the detector continues its gas monitoring
function. The display is not damaged and recovers when the temperature rises back above -20 °C.
Operating Humidity
Continuous 20-90%RH (non condensing), Intermittent 10-99%RH (non condensing)
Operating Pressure
90-110kPa
Storage Conditions
-25°C to +65°C (-13°F to +149°F)
16 to 32Vdc (24Vdc nominal)
Max 5 Watts. at 24Vdc (see section 2 regarding maximum in
rush current)
4-20mA (Source or Sink)
Fault (refer to table 5 section 12.3 for further details).
Normal gas measurement
Inhibit (during confi
Maximum over range
15 x screw terminals suitable for wire diameter 0.5mm
2.5mm
3 x 5A@250VAC. Selectable normally open or normally closed
(switch) and energized/de-energized (programmable).
RS485, Modbus RTU(Pending)
Steps
Selectable
Default Cal
Response
Cal Gas
Point
Time (T60)
Range
Secs
10%LEL
50%LEL
25 to 95% of
selected full
n/a
10%LEL
scale range
10%LEL
50%LEL
705 Sensor
705HT
Calibration gas
*6
50% Hydrogen/air
*7
50% Methane/air
*4
50% Butane/air
*5
50% Propane/air
*4
50% Pentane/air
*6
50% Ethylene/air
47
SPXCDHMRFENU Issue 1
guration/user settings)
2
(20AWG to 13AWG).
Response
Accuracy
Operating Temperature
Time (T90)
Secs
Min
<25
<+/- 1.5%LEL -55°C / -67°F 80°C / 176°F
<25
<+/- 1.5%LEL -55°C / -67°F 150°C / 302°F 10%LEL ▲
<6
<10
<+/- 1.5%LEL -55°C / -67°F 150°C / 302°F 20%LEL ▲
705HT Sensor
Adjust to
Calibration gas
50%
50% Hydrogen/air
50%
50% Methane/air
50%
50% Butane/air
50%
50% Propane/air
50%
50% Pentane/air
50%
50% Ethylene/air
2
to
Default Alarm Points
Max
A1
A2
20%LEL ▲
40%LEL ▲
15%LEL ▲
40%LEL ▲
▲ - Rising Alarm ▼ - Falling Alarm
Adjust to
50%
50%
50%
50%
50%
50%